Figure 2-4 Motor Connections without Output Contactor
See Appendix C For Recommended Terminal Tightening Torques
A motor circuit contactor is recommended to provide a positive disconnection to prevent motor
rotation which could pose a safety hazard to personnel or equipment. Open the Enable input to J1
terminal strip at least 20 msec before main M-contacts open to prevent arcing at contacts. This
greatly increases contactor life and allows use of IEC rated contactors. See Figure 2-5 for motor
connection with M-contactor.
Figure 2-5 Typical Connection using Output M-Contactor
See Appendix C For Recommended Terminal Tightening Torques
2-13
INSTALLATION
50/60 HZ
3 Phase
Power
MOTOR
GND T3
T2
T1
Breaker or Fuse Protection -
Customer Option, Subject
to Local Codes
GND
R2
B+\R1
T3
T2
T1
L3
L2
L1
GND
ENABLE
7
8
9
J1-8 CONNECTION
M
J1
ENABLE
M
T1
T2
T3
GND
M
MN723H-10/95 11/28/95 1:09 AM Page 25 (Black plate)