Resolver Wiring
The 23H control requires the use of resolver feedback from the motor shaft. The resolver power and
signal connections are made to the control's J1 terminal strip.
Resolver wiring must be twisted shielded pairs, #22 AWG minimum size, 150' maximum, with an
insulated overall shield. Connect all shields to J1-29. Maximum wire-to-wire or wire-to-shield
capacity shall not exceed 7500 picofarads per pair (50 pf/foot at 150' length).