Section 3
Receiving and Installation
MN715J
Receiving and Installation 3-1
Receiving & Inspection
The Series 15J Inverter Control is thoroughly tested at the factory and
carefully packaged for shipment. When you receive your control, there are
several things you should do immediately:
1.
Observe the condition of the shipping container and report any damage
immediately to the commercial carrier that delivered your control.
2.
Verify that the control you received is the same as listed on your
purchase order.
3.
If the control is to be stored for several weeks before use, be sure that it
is stored in a location that conforms to published storage specifications.
(Refer to Section 6 of this manual).
Physical Installation
The mounting location of the 15J is important. It should be installed in an area
that is protected from direct sunlight, corrosives, harmful gases or liquids,
dust, metallic particles, and vibration. Exposure to these elements can reduce
the operating life and degrade performance of the control.
Several other factors should be carefully evaluated when selecting a location
for installation:
1.
For effective cooling and maintenance, the control should be mounted
on a smooth, non-flammable vertical surface. Table 3-1 lists the Watts
Loss ratings for enclosure sizing.
2.
At least two inches clearance must be provided on all sides for airflow.
3.
Front access must be provided to allow the control cover to be opened
or removed for service and to allow viewing of the Keypad Display.
4.
Altitude derating.
Up to 3300 feet (1000 meters), no derating required.
Above 3300 feet, derate output current by 2% for each 1000 feet above
3300 feet.
5.
Temperature derating.
Up to 40
°
C, no derating required. Above 40
°
C,
derate output current by 2% per
°
C above 40
°
C.
Maximum ambient is 55
°
C.
Table 3-1 Series 15J Watts Loss Ratings
115VAC
230VAC
460VAC
2.5kHz
PWM
7.5kHz
PWM
2.5kHz
PWM
7.5kHz
PWM
2.5kHz
PWM
7.5kHz
PWM
17 Watts/
Amp
20 Watts/
Amp
17 Watts/
Amp
20 Watts/
Amp
19 Watts/
Amp
28 Watts/
Amp
Control Installation
The control must be securely fastened to the mounting surface. Use the four
(4) mounting holes to fasten the control to the mounting surface or enclosure.
Shock Mounting
If the control will be subjected to levels of shock greater than 1G or vibration
greater than 0.5G at 10 to 60Hz, the control should be shock mounted.
Excessive vibration within the control could cause internal connections to
loosen and cause component failure or electrical shock hazard.
Summary of Contents for ID15J101-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual ...
Page 5: ...iv Table of Contents MN715J ...
Page 11: ...2 4 General Information MN715J ...
Page 59: ...4 22 Programming and Operation MN715J ...
Page 75: ...6 6 Specifications and Product Data MN715J ...
Page 79: ...A 4 Dynamic Brake Hardware MN715J ...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1 ...