4-18 Programming and Operation
MN715J
Parameter Block Definitions
Level 2
OUTPUT LIMITS
MIN Output Frequency
The minimum output frequency to the motor. During
operation, the output frequency will not be allowed to go below this value except
for motor starts from 0 Hz or during dynamic braking to a stop.
MAX Output Frequency
The maximum output frequency to the motor.
PK Current Limit
The maximum output (peak) current to the motor. Values above
100% of the rated current are available depending upon the operating zone
selected.
PWM Frequency
The frequency that the output transistors are switched. PWM
should be as low as possible to minimize stress on the output transistors and
motor windings. PWM frequency is also referred to as “Carrier” frequency.
PROTECTION
External Trip
OFF - External Trip is Disabled. (Ignores J4-17).
ON - External Trip is enabled. If a normally closed contact at J4-17 (to J4-18) is
opened, an External Trip fault will occur and cause the drive to shut down.
Foldback Protect
OFF - Foldback protection is disabled.
ON - Acceleration rate is extended automatically to help prevent overcurrent trips
during rapid acceleration.
MISCELLANEOUS
Restart Auto/Man
Manual
If a fault occurs (or power loss), the control must be manually reset to
resume operation.
Automatic
- If a fault occurs (or power loss), the control will automatically reset
(after restart delay) to resume operation.
Restart Fault/Hr
The maximum number of automatic restart attempts before
requiring a manual restart. After one hour without reaching the maximum number
of faults or if power is turned off and on again, the fault count is reset to zero.
Restart Delay
The amount of time allowed after a fault condition for an automatic
restart to occur. Useful to allow sufficient time to clear a fault before restart is
attempted.
Language Select
Selects English, Spanish, French, German, Italian or Portuguese
characters for keypad display.
Factory Settings
Restores factory settings for all parameter values.
Select “YES” and press “ENTER” key to restore factory parameter values. The
keypad Display will show “Operation Done” then return to “NO” when completed.
Summary of Contents for ID15J101-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual ...
Page 5: ...iv Table of Contents MN715J ...
Page 11: ...2 4 General Information MN715J ...
Page 59: ...4 22 Programming and Operation MN715J ...
Page 75: ...6 6 Specifications and Product Data MN715J ...
Page 79: ...A 4 Dynamic Brake Hardware MN715J ...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1 ...