MN715J
Programming and Operation 4-21
Parameter Block Definitions
Level 2 Continued
SKIP FREQUENCY
Skip Frequency
(#1, #2 and #3) The center frequency of the frequency band to skip
or treat as a speed command dead-band.
Skip Band
(#1, #2 and #3) The width of the band centered about the Skip Frequency.
For example, if Skip Frequency #1 is set to 20Hz and Skip Band #1 is set to 5Hz,
continuous operation is not allowed in the dead-band of 15Hz to 25Hz.
Note: Three bands can be defined independently or the three values can be
selected to skip one wide frequency band.
SYNCHRO STARTS
Sync Start Enable
Allows Synchro Starts.
Sync Scan V/F
Sets the Volts/Hertz ratio for the Synchro Starts feature as a
percentage of the V/Hz ratio defined by the Max Output Volts/Base Frequency.
This Sync Scan V/F percentage value is multiplied by the Max Output Volts/Base
Frequency value. If this value is too high, the inverter may fault on Over-Current.
Sync Setup Time
The time for the inverter to ramp the output voltage from zero to
the voltage that corresponds to the frequency set by the “Sync at Max Freq”
parameter. A 0.5 second delay before the ramp begins is not included in this
time. If the Synchro Starts feature is not operating quickly enough, decrease the
Sync Setup Time value.
Sync Scan Time
The time allowed for Synchro Starts to scan and detect rotor
frequency. Generally, the shorter the Sync Scan Time the more likely a false
Synchro Starts will be detected. This value should be set high enough to
eliminate false Synchro Starts.
Summary of Contents for ID15J101-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual ...
Page 5: ...iv Table of Contents MN715J ...
Page 11: ...2 4 General Information MN715J ...
Page 59: ...4 22 Programming and Operation MN715J ...
Page 75: ...6 6 Specifications and Product Data MN715J ...
Page 79: ...A 4 Dynamic Brake Hardware MN715J ...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1 ...