13
2 QUICK-START INSTRUCTIONS
Important:
You must read these simplified instructions before proceeding. These instructions
are to be used as a reference only and are not intended to replace the details provided herein.
You must read the Safety Notice on, page 11, before proceeding.
2.1 Connections
(See Figure 3, on page 14).
2.1.1
AC Line.
Connect AC line voltage to terminals L1 and L2. Be sure jumpers J2A and J2B are both
set to the correct input line voltage 115 or 230 VAC. Connect ground wire (earth) to
green ground screw on case.
2.1.2 Motor.
A.
Permanent Magnet (PM) Type. Connect motor armature leads to A1 (+) and A2 (–).
Be sure jumper J3 is set to the proper position “90V" for 90 volt DC motors and
“180V" for 180 volt DC motors.
Note: 180 volt DC motors must be used with 230 VAC line, 90 volt motors can be used
with a 230 VAC or 115 VAC line. See Section 6.3, on page 26.
B.
Shunt Wound Motors. Connect motor armature as above. Connect full voltage
shunt field wires (90 volt motors with 100 volt fields and 180 volt motors with 200
volt fields) to F1 and F2. Connect half voltage field wires (90 volt motors with 50
volt fields and 180 volt motors with 100 volt fields) to F1 and L1. See Section 4,
on page 16.
2.2 Speed or Torque Mode –
Jumper J1 is factory set for speed control operation ("SPD"). For
torque control, set J1 to "TRQ" position. See Section 6.1, on page 23.
2.3 Armature Current -
Jumper J4 is factory set for 10 amp motors (10A). For lower amperage
motors, place J4 in the proper position. See section 6.4, on page 27 for details.
Note: The factory setting for Current Limit is 150% of the nominal current setting, e.g., if J4 is
selected for 10 amps, the actual CL setting will be 15 amps.
2.4 Trimpot Settings –
All trimpots have been factory set in accordance with Figure 3, on page
14. See Table 3, page 6, for descriptions.
2.5 Diagnostic LEDs –
After power is turned on, observe LED’s to verify proper control function.
See Section 9, on page 34.
2.6 Armature Fuse -
The correct size armature fuse
must be installed
, depending on the rating
of the motor. Control will not operate if fuse is not installed. See Section 4.1.2, page 16 and
Table 7, on page 17.
2.7 START/STOP Switch -
The BC154 / BCWD140 contains a built-in manual start/stop
switch. This switch must be used to start the control each time AC power is lost. To
override this function, see Section 4.7.3, on page 20.
Summary of Contents for NEMA-4X
Page 37: ...37 Notes...
Page 38: ...38 Notes...