7-2 Specifications
MN1903
7.1.3 Analog outputs (Drive Demand/Command - X7)
Description
Unit
Value
Type
Bipolar
Output voltage range
VDC
±10
Output current (max)
mA
1
Output DAC resolution
bits
14
(includes sign bit)
Equivalent resolution
mV
±1.22
Update interval
Immediate
7.1.4 Digital inputs (X1 & X2)
Description
Unit
Value
Type
VDC
Opto-isolated, AC inputs
Input voltage (Active high)
Nominal
Minimum
VDC
24
12
Input voltage (Active low)
Nominal
Maximum
VDC
0
2
Input current
(approximate, per input)
mA
8
Sampling interval
ms
1
7.1.5 Digital inputs (X3)
Description
Unit
Value
Type
VDC
Non-isolated, AC inputs
Input voltage (Active high)
Nominal
Minimum
VDC
24
12
Input voltage (Active low)
Nominal
Maximum
VDC
0
2
Input current
(approximate, per input)
mA
8
Sampling interval
ms
1