To Broadcast An Emergency Recorded Message, Preceeded by “Start of Test”
and concluded by “End of Test” Message
1)
)
Lift plastic cover and depress Switch.
The ‘Emergency Enable’ indicator will illuminate
2)
Zone Available
Currently silent (no broadcast
3)
Press zone select of the desired zone or zones.
Zone Selected
If no zones are selected an ‘All Call’ will be performed.
4)
Press Test Message, e.g. message 6
Broadcasting Message 6
“Start of Test”.
5)
Allow the message to sound at least once, and then either set the Fire Detection System into the Fire Alarm
condition or select the appropriate message (e.g. Evacuate – Message 1) as shown below.
6)
Press the zone select of the desired zone or zones
Zone selected, currently
broadcasting Start of Test,
Message 6
7)
Select message, e.g. Evacuate (message 1)
Broadcasting message 1
Evacuate
8)
At the end of the test,
Broadcasting message 1
Press zone select of the desired zone or zones
9)
Press cancel to cancel message selected in
Broadcasting message 7
step (8) and broadcast End of Test, message 7.
“End of Test”.
10)
At the end of the ‘End of Test’ message the zone
No broadcast
will automatically clear.
EMERGENCY
ENABLE