Care2
Installation Instructions
Care2 issue 7
55
4.9 S
YSTEM
M
ENU
S
TRUCTURE
4.9.1 System Parameters
Title
Description
Change PIN
Change the PIN to access the System Menu
Local System Status View the Status of the Local Console
Local Device Status View the Status of the Local Internal Devices
Local Line Status
View the Status of each Line of the Console
Vendor Details
View and Change the Vendor Contact details
System Parameters
View and Adjust settings relating to the system
Line Parameters
View and adjust settings relating to the Line and
relevant Outstation
RTC Adjustment
Set the Real Time Clock
Exit
Exit from System Menu
Title
Default Value
Description
Local Address
1
Sets the Network Address of the Local Panel
DTA Resetable
No
Reset Active DTA calls from Console
BBU Monitored
Yes
Battery Backup Fault Monitoring
DRS Enable
N-Open
** DRS Enable Contacts set to Normally Open **
DRS PF Enable
Yes
Enable DRS Remote Units on Mains Power Failure
RTC in ScnSvr
No
Show Real Time Clock on ScreenSaver
Fault Silence
No
Temporarily disable Fault Sounder
IC Call Silence
No
Temporarily disable Incoming Call Sounder
Silence Timeout
480mins
Timeout before Fault & Incoming Call Sounders
are reactivated
LCD Timeout
60secs
Timeout for LCD to return to Screensaver
LCD Contrast
37%
LCD contrast
Fault Repeat
480mins
Timeout before Faults are reannounced
Warning Repeat
720mins
Timeout before Warnings are reannounced
CH Type
CH
Type of Console Handset on Local Console
CH Name
Main Console
Name of local Console
CH Offhook 1
>1600uA
Threshold for Handset Offhook
CH Onhook 1
<9600uA
Threshold for Handset Onhook
CH EOLz OC 1
<400uA
Threshold for Open Circuit Handset Fault
CH EOLz SC 1
>46400uA
Threshold for Short Circuit Handset Fault
Restore Defaults
N/A
Restore All System Settings to Default Values
Exit
Exit System Parameters Menu
** This setting must be set to N-Closed when a Fire Panel Interface is required