BAM PC-OS-024-_ _ K-1

Protective Housing

Use and testing 
Device category and suitability II

The protective housing as a piece of equipment is divided 

into Equipment Category II, i.e. for all explosion hazard 

areas except for potentially explosive areas with the 

exception of mine workings susceptible to firedamp. It may 

be used in accordance with the following description in 

areas subject to dust explosions.

Dust explosion protection II 3D, 

Equipment Protection Level (EPL) Dc

The Equipment Category II 3D with EPL Dc includes 

equipment with "increased" protection level for use 

in flammable dust atmospheres where there is no ignition 

hazard during normal operation and which has additional 

protection measures which ensure that there is no 

danger of ignition when expected fault conditions occur.

Protection by enclosures tc

A rating of tc means that no combustible dust can enter.

Dust Group IIIC

Dust Group IIIC includes possible use with conductive 

dusts, non-conductive dust and combustible lint.

Temperature Class T90°C

The temperature specification T90°C indicates that the 

surface temperature of the uncooled housing during 

normal operation lies within the permissible specification 

under all conditions at maximum 90 °C.

ATEX safety instructions (continued)

Notes for installation, operation and repair 

 

– Only sensors from the BOS 23K-…/BOD 23K-… and 

BOS 50K-…/BOD 50K-… series may be installed in 

the housing.

 

– Refer to Section 4 for installation.

 

– The protective housing may be installed on the 

machine in any orientation.

 

– The connection cable must be suitable for the 

application area and routing must be according to the 

requirements (fixed installation, protected against 

damage, etc.).

 

– The O-Ring Ø73 X Ø3 FKM75 (BAM PC-OS-024-23K-1) 

and Ø93 X Ø3 FKM75 (BAM PC-OS-024-50K-1) must 

be correctly installed and dust sealing of the housing 

ensured.

 

– The protective housing is attached to the machine 

using four M5 screws.

 

– The cover screw may be opened only for startup when 

there is no dust atmosphere present.

 

– During operation the cover screw must be closed so 

that it remains dust-tight.

 

– Dust buildup must be regularly removed.

 

– In explosion hazard areas the protective housing may 

be used only at a permissible ambient temperature of 

–5…+70 °C.

 

– In accordance with the conditions of use the protective 

housing must be regularly inspected for damage.

 

– If a malfunction occurs or damage becomes evident, 

immediately take the system out of service for repair.

 

– Damaged parts must be replaced only by original 

replacement parts. 

 

– The plugs may be plugged in or disconnect only when 

de-energized.

The following warning label is enclosed and must be 

attached in a clearly visible manner:

 

– The device has to be protected against impacts with 

high impact energy.

Summary of Contents for BAM PC-OS-024-23K-1

Page 1: ...deutsch Betriebsanleitung english User s Guide BAM PC OS 024 23K 1 BAM PC OS 024 50K 1 ...

Page 2: ...www balluff com ...

Page 3: ...2013 EN 60079 31 2014 2011 65 EU RoHS Richtlinie RoHS Directive EN 50581 2012 Kennzeichnung II 3D Ex tc IIIC T90 C Dc Marking II 3D Ex tc IIIC T90 C Dc Konformitätsbescheinigung EPS 16 ATEX 1 107 X Certificate of Conformity EPS 16 ATEX 1 107 X Die Hinweise in der Betriebsanleitung sind zu beachten The operation manual document must be followed Die technische Dokumentation wird beim Hersteller arch...

Page 4: ......

Page 5: ...Februar 2014 die Erfüllung der grundlegenden Sicherheits und Gesundheitsanforderungen für die Konzeption und den Bau von Geräten und Schutzsystemen zur bestimmungsgemäßen Verwendung in explosionsgefährdeten Bereichen gemäß Anhang II der Richtlinie Die Ergebnisse der Prüfung sind in der vertraulichen Dokumentation unter der Referenznummer 16TH0224 festgelegt 9 Die grundlegenden Sicherheits und Gesu...

Page 6: ...zum mechanischen Schutz des eingebauten Sensors Das Schutzgehäuse eignet sich zum Einsatz in explosionsgefährdeten Bereichen mit brennbaren Staubatmosphären entsprechend der Kennzeichnung Elektrische Daten Betriebsspannung 24 V DC Betriebsstrom 30 bis 60 mA 16 Referenznummer 16TH0224 17 Besondere Bedingungen Die Stecker dürfen nur im spannungslosen Zustand gesteckt bzw getrennt werden Das Gerät is...

Page 7: ...ial Health and Safety Requirements relating to the design and construction of equipment and protective systems intended for use in potentially explosive atmospheres given in Annex II of the Directive 2014 34 EU The examination and test results are recorded in the confidential documentation under the reference number 16TH0224 9 Compliance with the Essential Health and Safety Requirements has been a...

Page 8: ...29L C is used for the mechanical protection of the build in sensor The protective housing is suitable for the use in hazardous areas with flammable dust atmospheres in accordance with the marking Electrical data Rated voltage 24 V DC Rated current 30 to 60 mA 16 Reference number 16TH0224 17 Schedule of Limitations The plugs may be plugged in or disconnect only when de energized The device has to b...

Page 9: ...BAM PC OS 024 23K 1 BAM PC OS 024 50K 1 Betriebsanleitung deutsch ...

Page 10: ...en darf das Schutzgehäuse nicht in Betrieb genommen werden Nehmen Sie in diesem Fall Kontakt mit Balluff auf Entsorgung Befolgen Sie die nationalen Vorschriften zur Entsorgung Sicherheitshinweise ATEX Bestimmungsgemäße Verwendung Dieses BAM Schutzgehäuse dient zum mechanischen Schutz des eingebauten Sensors Das Schutzgehäuse eignet sich zum Einsatz in explosions gefährdeten Bereichen mit brennbare...

Page 11: ...ürfen nur Sensoren der Bau reihen BOS 23K BOD 23K und BOS 50K BOD 50K eingebaut werden Die Montage erfolgt entsprechend Kapitel 4 Montage Das Schutzgehäuse kann in beliebiger Lage an der Maschine montiert werden Das Anschlusskabel muss für den Einsatzbereich geeignet sein und die Verlegung muss entsprechend den Anforderungen erfolgen feste Verlegung Schutz gegen Beschädigung etc Der O Ring Ø73 X Ø...

Page 12: ...tsch BAM PC OS 024 _ _K 1 Schutzgehäuse Montage Abmaße BOS50K BOS23K 57 60 33 20 29 8 67 8 Schritt 1 4 1 5 Nm 50 K 3 1 5 Nm 23 K 1 2 3 4 Schritt 2 24 10 12 Nm 5 6 Schritt 3 4 5 7 Nm 7 Schritt 4 8 Schritt 5 9 ...

Page 13: ... Zubehör Zubehör bitte separat bestellen Bezeichnung Typenschlüssel Bestellcode Wasseranschlussteile für 23K BAM PC OS 026 23K 1 BAM029K Wasseranschlussteile für 50K BAM PC OS 026 50K 1 BAM029P Luftvorhang BAM AN AM 001 01 1 BAM029N Ersatzdeckel Glas 23K BAM PC OS 024 23K G RK BAM029E Ersatzdeckel Glas 50K BAM PC OS 024 50K G RK BAM029H Kabel 5 m BCC S415 0000 1A 003 PX0434 050 BCC0EZ9 Kabel 10 m ...

Page 14: ......

Page 15: ...english BAM PC OS 024 23K 1 BAM PC OS 024 50K 1 User s Guide ...

Page 16: ...e used the protective housing many not be placed in service In such cases please contact Balluff Disposal Observe the national regulations for disposal ATEX safety instructions Intended use This BAM protective housing is used for mechanical protection of the installed sensor The protective housing is suitable for use in explosion hazard areas with flammable atmospheres in accordance with the desig...

Page 17: ...ions continued Notes for installation operation and repair Only sensors from the BOS 23K BOD 23K and BOS 50K BOD 50K series may be installed in the housing Refer to Section 4 for installation The protective housing may be installed on the machine in any orientation The connection cable must be suitable for the application area and routing must be according to the requirements fixed installation pr...

Page 18: ...lish BAM PC OS 024 _ _K 1 Protective Housing Installation Dimensions BOS50K BOS23K 57 60 33 20 29 8 67 8 Step 1 4 1 5 Nm 50 K 3 1 5 Nm 23 K 1 2 3 4 Step 2 24 10 12 Nm 5 6 Step 3 4 5 7 Nm 7 Step 4 8 Step 5 9 ...

Page 19: ...ed in explosion hazard areas Accessories Please order accessories separately Description Type Code Ordering Code Water connection for 23K BAM PC OS 026 23K 1 BAM029K Water connection for 50K BAM PC OS 026 50K 1 BAM029P Air blow off BAM AN AM 001 01 1 BAM029N Protective cover for housing 23K BAM PC OS 024 23K G RK BAM029E Protective cover for housing 50K BAM PC OS 024 50K G RK BAM029H Cable 5 m BCC...

Page 20: ...e 9 73765 Neuhausen a d F Phone 49 7158 173 370 Fax 49 7158 173 691 service balluff de US Service Center USA Balluff Inc 8125 Holton Drive Florence KY 41042 Phone 859 727 2200 Toll free 1 800 543 8390 Fax 859 727 4823 technicalsupport balluff com CN Service Center China Balluff Shanghai trading Co ltd Room 1006 Pujian Rd 145 Shanghai 200127 P R China Phone 86 21 5089 9970 Fax 86 21 5089 9975 servi...

Reviews: