22
english
3.6
Events
Event Code Event Type
Event – Description – Remedy
Device Status
0x1850
(6224)
Notification
Process data profile selection cannot be used –
default value is used.
0 – Device is operating properly.
0x1851
(6225)
Notification
Process Data Update Timeout
– For information
purposes only.
0 – Device is operating properly.
0x1852
(6226)
Warning
Multiple
Process Data Update Timeout
– For
information purposes only.
0 – Device is operating properly.
0x4000
(16384)
Error
Temperature Fault – Overload
– The device is
operated outside of the device-specific temperature
limits. Risk of device damage.
4 – Failure
0x4210
(16912)
Warning
Device Temperature Overrun – Clear Heat Of Source
– Risk of device damage. The device is too hot.
►
Remove heat source, provide the device with
heat insulation if necessary.
2 – Out-of-Specification
0x4220
(16928)
Warning
Device Temperature Underrun – Insulate Device
–
Risk of device damage. The device is too cold.
►
Insulate the device.
2 – Out-of-Specification
0x5110
(20752)
Warning
Primary supply voltage exceeded
►
Check for deviations in the supply.
2 – Out-of-Specification
0x5111
(20753)
Warning
Primary supply voltage below minimum value
►
Check for deviations in the supply.
2 – Out-of-Specification
0x8CB7
(36023)
Warning
One of the Speed Monitoring channels went below
the lower limit.
►
Check Speed Monitoring.
0 – Device is operating properly.
0x8CB8
(36024)
Warning
One of the Speed Monitoring channels exceeded the
upper limit.
►
Check Speed Monitoring.
0 – Device is operating properly.
0x8D05
(36101)
Warning
Measurement error/redundancy check failed.
►
Check application.
2 – Out of Specification
0x8D07
(36103)
Warning
The calculation of the basic statistics was stopped
automatically to avoid a buffer overflow.
0 – Device is operating properly.
0x8D0B
(36107)
Warning
Overload or short circuit at pin 2
►
Check wiring.
2 – Out-of-Specification
0x8D0D
(36109)
Warning
Incorrect load/cable breakage, analog current output
pin 2
►
Check wiring or connected devices.
2 – Out-of-Specification
0x8D0E
(36110)
Notification
The time has elapsed. This event reports the timeout
of the minimum value/maximum value/average
calculation.
It does not report a timeout for the calculation of the
moving average because the timer repeats and it
does not indicate the end of the calculation.
0 – Device is operating properly.
0x8D10
(36112)
Warning
Device Temperature Upper Warning
– The set upper
temperature warning threshold has been exceeded.
0 – Device is operating properly.
0x8D13
(36115)
Warning
One or more extreme conditions present.
0 – Device is operating properly.
0x8D15
(36117)
Warning
Overload at pin 2
►
Check wiring.
2 – Out-of-Specification
3
Overview of IO-Link Data and Functions (continued)
BCS Q40BBAA-PIM20C-EP _ _ _ -GS04
Capacitive Proximity Switches
Summary of Contents for BCS Q40BBAA-PIM20C-EP-GS04 Series
Page 1: ...BCS Q40BBAA PIM20C EP___ GS04 deutsch Konfigurationsanleitung english Configuration Guide...
Page 2: ...www balluff com...
Page 3: ...BCS Q40BBAA PIM20C EP___ GS04 Konfigurationsanleitung deutsch...
Page 4: ...www balluff com...
Page 87: ...BCS Q40BBAA PIM20C EP___ GS04 Configuration Guide english...
Page 88: ...www balluff com...
Page 171: ......