BIS V-6108 PROFINET
Processor Unit
26
english
This parameter indicates how often the 5-byte ID of a BIS L-1_ _-03 data carrier is imported and
compared before the data carrier is shown as identified. The value default setting is 2. For highly
dynamic applications, this value can be set to 1 (only BIS VL).
The cycle time controls the timing for triggering the IO-Link device. The factory default setting is
0 (Auto). It is recommended that this value be retained.
The cycle time is stored in the IO-Link device (slave) and is detected automatically. Only times
that are slower than the automatically selected times can be set manually.
The offset (offset data window) can be used by the start byte with length (length data window) to
define the end byte of the process data. This setting is only for the input data, has no influence
on the actual process data length and is for visual purposes only.
Whether a connected IO-Link device receives access to the IO-Link master can be controlled
using validation.
Configuration options:
– 0
No validation
– 1 Compatible
Only allows communication to the IO-Link master for devices whose vendor ID (VID) and
device ID (DID) correspond to the configured values.
– 2 Identical
See "1 Compatible"; in addition, the serial number of the IO-Link device is checked
Vendor ID for the IO-Link device (refer to the manual for the device)
Device ID for the IO-Link device (refer to the manual for the device)
Serial number for the IO-Link device (if available; refer to the IO-Link device's type plate)
UID Compare
Count
Cycle time
Offset data
window and
Length data
window
Validation type
Vendor ID, VID
Device ID, DID
Serial number
(SerNum),
optional