www.balluff.com
BIS V-6108 PROFINET
Processor Unit
53
english
Command Identifier 46
hex
: Read out Transmission Power
Reads out the current transmission power (ERP). The transmission power is returned as a value
in the form of quarter dBm.
Example:
Reading out the transmission power returns the value of 54
hex
(= 84).
This corresponds to a transmission power of 21 dBm: 84/4 = 21
Subaddress
Meaning
Description of Function
00
hex
1st Bit Header
01
hex
Command Identifier 46
hex
: Read out antenna power.
…
None
No meaning
Last byte
2nd Bit Header
If the 1st and 2nd bit headers match, the data is valid.
If execution is successful, the response is passed to the input buffer in the following format:
Subaddress
Meaning
Description of Function
00
hex
1st Bit Header
01
hex
Antenna power
Antenna power in increments of n * 0.25 dBm or 0 for
disconnected antennae.
Example:
An antenna power of 20 dBm corresponds to a value of
80
hex
.
…
None
No meaning
Last byte
2nd Bit Header
Valid data is present if the 1st and 2nd bit strings
match.
or
Input Buffer: Status Message
Subaddress
Meaning
Description of Function
00
hex
1st Bit Header
01
hex
Status code
Provides information on the status of a query.
…
None
No meaning
Last byte
2nd Bit Header
If the 1st and 2nd bit headers match, the data is valid.
Specific
commands for
BIS VU read/write
heads
7
Device Functions