background image

6.  RFID  Controller  Connection:  Connect  the  male  end  of  a  5-pin, 

male-to-female,  ThinNet  drop  cable  to  the  female  end  on  your 
Drop-T  connector(s).  Attach  the  remaining  female  end  of  the 
ThinNet drop cable to the 5-pin, male, M12 connector on a

 BIS U

BIS  M-6xx  or  BIS  M-41x  (RS485  models).  Repeat  Step  5  for 
each RFID controller you plan to install. 

Note: maximum drop cable length is 2 m. 

Subnet16™ Power Supply Wiring: For ThinNet Networks: Using a 5-
pin, female,  M12,  ThinNet  connector  (

P/N:  BCC06ZF), make  a  power 

cable and connect it to your power supply (SHIELD wire connected to 
Earth). Attach the female, ThinNet end to the 5-pin, male, ThinNet end 
on a Drop-T connector (

P/N: BCC07WR). 

7 .   Gateway Power and Host Connection: Connect the Gateway to 

the  DeviceNet  network  via  a  DeviceNet-compatible  interface 
cable.  The  Gateway  must  be powered  through pins  V+  and  V-  of 
the DeviceNet connector. 

8 .   Power  On:  Turn  both  power  supplies  ON.  The  POWER  LED  on 

the  Gateway  will  remain  lit  while  power  is  applied  to  the  unit 
through the DeviceNet connector. 

9 .   Automatically Configure Subset16™ Node IDs: At this point all 

controllers are powered  and should  have  Node  IDs set  to 00,  (all 
controller  Node  LEDs  =  OFF),  and  Subnet16™  baudrate  =  9600 
(factory defaults). 

a.  Place  the  RFID  Controller  Configuration  Tag  in  front  of  an 

RFID  Controller  (the  controller's  RF  Activity  LED  blinks  once 
indicating the tag has been read), and wait for the Gateway to 
assign  a  valid  Node  ID  to  it.  The  controller's  Node  LEDs  now 
indicate  a  valid  Node  ID.  Remove  the  Configuration  Tag  from 
the controller. 

b.  Repeat  this  step  for  each  node  in  the  Subnet16™  network 

(one controller at a time). The first is Node ID 1, then 2 and so 
on up to 16 (binary). 

 
The Subnet16™ network is now configured with the default values and 
can  communicate  with  the  DeviceNet  Gateway  which  in  turn 
communicates with the DeviceNet Master. 

 

BIS Z-GW-001-DNT DEVICENET FACTORY DEFAULTS: 

Node Address:  63; Baud Rate: 125 kbps 

 

For  further  information  or  for  application  specific  configuration  using 
the Dashboard Configuration Tool program, see the Gateway Manual. 
 

DIMENSIONS 

 

POWER REQUIREMENTS 

The DeviceNet Gateway requires an electrical supply voltage of 
12  to  30  Vdc.  It  is  powered  through  the  DeviceNet  network 
connector. 

In addition, each RFID controller connected to the Gateway via 
the Subnet16™ network will also require power. This network is 
powered  separately.  Use  a  regulated  power  supply  that  is 
capable  of  delivering  the  requirements  listed  in  the  Technical 
Features. 

 

 

NOTE 

Power  is  applied  directly  to  the  Subnet16™  Network 
trunk  and  distributed  through  drop  cables  to  the  RFID 
controllers.  By  positioning  the  power  supply  near  the 
middle  of  the  network,  you  can  limit  voltage  drop  at  the 
ends, (see example layouts). 

 
The  following  information  is  provided  to  assist  you  in 
determining the power requirements of your RFID application. 
 
 

System Current Consumption 

 

 

NOTE 

The  current  consumption  values  of  each  product  are 
given in the Technical Features paragraph of the relative 
Installation  manual  and  refer  to  the  min  and  max  input 
voltage  range.  These  values  already  include  an 
adequate  safety  margin.  The  consumption  values  given 
in  the  following  examples  have  been  interpolated  for  an 
input voltage of 24 Vdc. 

 
Max Gateway Current: 200 mA @ 12 Vdc (133 mA @ 24 Vdc). 
 
Max Processor  Current:   366 mA @ 24 Vdc for BIS M-6xx-Series, 87 
mA @ 24 Vdc for BIS M-41X-Series, etc. (refer to Processor ’s spec). 
 
Calculating Subnet16™ System Current Consumption: 

Subnet16™ System Current Consumption = (Max Controller 
Current x Number of Controllers) 

 
Example 
A Subnet16™ network powered at 24 Vdc is composed of a BIS Z-GW-
001-DNT   connecting eight BIS M-41X-485 Processor s. 
 
Subnet16™ System Current Consumption = (0.087 A X 8)] = 0.696 A 
 

Cable Voltage Drop 

 

In addition, each RFID controller on the Subnet will experience a certain 
amount of voltage drop depending on the length of the cable. 

Cable Resistance per Meter 

 

ThinNet = 0.058 ohms per meter per wire 

 

ThickNet = 0.0105 ohms per meter per wire 

 
Calculating Voltage Drop 

Voltage Drop = 

(Max Controller Current x Number of Controllers) x 
(Cable Resistance per Meter per Wire 

1 x Cable length 

in Meters) 

 

Example 
A  Subnet16™  network  is  composed  of  a  BIS  Z-GW-001-DNT   
connecting eight BIS M-41X-485 Processors (87 mA each @ 24 Vdc). A 
total  of  20  meters  of  ThinNet  cables  are  used  to  connect  the  devices, 
which  have  Cable  Resistance  =  0.058  Ohms  per  meter  per  wire.  The 
network power is 24 Vdc. 

2

 

Voltage Drop = 

(0.087 A x 8 controllers) x [(0.058 x 2) x 20 meters] = 
1.61 Vdc 

24 Vdc - 1.61 = 22.39 Vdc at controller number 8 

                                                           

1

 The resistance calculation must include both wires (Vdc and GND). 

2

  This  example  assumes  the  power  supply  is  placed  at  the  end  of  the 

network,  therefore  controller  #8  is  the  worst  case.  By  placing  the 
power  supply  in  the  middle  of  the  network  the  voltage  drop  at  the 
ends is reduced. 

It  is  recommended  that  the  voltage  drop  calculation  be  conducted  on 
the  RFID  controller  that  is  farthest  from  the  Gateway,  as  it  will 
experience the greatest voltage drop. 
 
 

Max Supported Trunk and Drop Cable Lengths 

 

 

ThickNet trunk length up to 300 m. 

 

ThinNet trunk length up to 20 m. 

 

ThinNet drop cable length up to 2 m. 

 
 

Current Rating for Cables 

 

The  maximum current  rating  for  the  Subnet16™  network  using 
Balluff cables and accessories (BCCxxxx), is 4.0 A
 
 

COMPLIANCE 

This  product  is  intended  to  be  installed  by  Qualified 
Personnel only. 
 
This product must not be used in explosive environments. 
 
See  the  Subnet16™  Gateway  Manual  for  the  Declaration  of 
Conformity. 
 
 

Power Supply 

 
This  device  is  intended  to  be  supplied  by  a  UL  Listed  or  CSA 
Certified Power Unit with «Class 2» or LPS power source. 
 
 

CE Compliance 

 
Warning: This is a Class A product. In a domestic environment 
this  product  may  cause  radio  interference  in  which  case  the 
user may be required to take adequate measures. 
 

 

 
 
 
 
 
 
 
 

mm 

in 

N

r.

 8

9

0

 4

1

3

 E

 

.

 E

d

it

io

n

 1

3

0

5

S

u

b

je

c

to

 m

o

d

if

ic

a

ti

o

n

Reviews: