background image

3

english

BNI IOL-314-S52-P012 / BNI IOL-314-S52-P071

Network interface – Digital hub

The supply voltage for the module is provided via the 

IO-Link interface from the higher-level IO-Link master.
There are three different supply voltages: U

S1

, U

S2

 and 

U

A

:

–  U

S1 

supplies the module and also the connected 

sensors. (Variant ...P012).

–  U

S1

 supplies the module only (Variant ...P071).

–  U

S2

 supplies the connected sensors. (Variant ...P071).

 

– U

A

 is the supply for the digital outputs.

IO-Link interface (XF1/

0 1

00

01

00

01

00

01

00

01

00

01

00

01

00

01

00

BNIXXXX

)

Plug

Pin

Signal BNI IOL-…

…-P012

…-P071

4

3

1

2

Top view of M12 

plug, A-coded

Supply voltage 

for the module 

and connected 

sensors (U

S1

)

Supply voltage 

for the module 

(U

S1

)

2

Supply voltage 

for actuators 

(U

A

)

3

GND, reference potential

4

C/Q, IO-Link data transmission 

channel

Auxiliary voltage connection (XD1)

The BNI IOL-314-S52-P071 variant has an L-coded M12 

auxiliary voltage connection. This connection allows more 

power to be supplied for the sensor and actuator systems.

Plug

Pin

Signal

Top view of M12 

plug, L-coded

Power supply U

S2

2

GND, reference potential U

A

3

GND, reference potential U

S2

4

Actuator supply U

A

5

Function ground

Current limitation when using the extension port

–  Variant BNI IOL-314-S52-P012

Observe the current limitation: The output is split 1:1 

between the first and second device.

–  Variant BNI IOL-314-S52-P071

There is no current limitation to consider because the 

current for the second device is supplied independently 

via the auxiliary voltage connection.

Power supply

NOTICE

Unwanted voltage dips

Non-separated electric circuits of the power supplies for 
sensor and actuator can lead to unwanted voltage dips 
of the sensor supply when switching actuators.

 

Fuse the power supplies for sensors and actuators 
separately.

 

Make sure that the power supply of the device is 
sufficiently dimensioned to cover start-up and peak 
currents and design the fuse protection concept 
accordingly.

NOTICE

Overcurrent

Defective or missing fuses in the power supply for sensor 
and actuator will damage them.

 

Use a fuse or intelligent power supply (current 
monitoring designed for max. 4 A for BNI IOL-…-
-P012 or 16 A for BNI IOL-…-P071).

 

Connect the protective earth conductor to the FE 
terminal.

 

Connect the incoming IO-Link line to the sensor hub.

NOTICE

Loss of function and property damage

Improper installation, e.g. due to misconnection or 
incorrect polarity of the connections, can result in a loss 
of the function and property damage.

 

Take measures to prevent misconnection or polarity 
reversal.

 

Prevent tampering at the connections.

 

Never exceed the value of 36 V between any of the 
pins.

If possible, supply power to the sensor/module 

and actuator using an independent power source 

to ensure independent operation in the event of a 

power failure.

For UL: observe cable requirements and power 

supply requirements (siehe section 

UL requirements)!

Electrical connection (continued)

Summary of Contents for BNI IOL-314-S52-P012

Page 1: ...BNI IOL 314 S52 P012 BNI IOL 314 S52 P071 deutsch Montageanleitung english Assembly instructions fran ais Notice de montage italiano Istruzioni di montaggio polski Instrukcja monta u...

Page 2: ...ichern Die BNI Module haben grunds tzlich eine gute Chemika lien und lbest ndigkeit Beim Einsatz in aggressiven Medien z B Chemikalien le Schmier und K hlstoffe jeweils in hoher Konzentration etwa dur...

Page 3: ...von 3 Nm unter Verwendung der Befestigungsl cher befestigen Voraussetzungen zum Einhalten der Schutzarten F r IP68 IP69K m ssen alle Stecker und Verschlusskap pen ordnungsgem angeschlossen und das An...

Page 4: ...enzung beachtet werden da ber den Hilfsspannungsanschluss der Strom f r das zweite Ger t unabh ngig zur Verf gung gestellt wird Spannungsversorgung ACHTUNG Ungewollte Spannungseinbr che Nicht getrennt...

Page 5: ...O ST SV oder R C AVLV2 gelistete Kabel die auf der UL Style Page als f r externe Verbindungen geeignet gekennzeichnet oder spezifiziert sind mit einem Nennwert von mindestens 300 V mindestens 14 AWG e...

Page 6: ...use The BNI modules generally have good chemical and oil resistance When used in aggressive media e g chemicals oils lubricants and coolants in high concentrations e g due to low water content the ma...

Page 7: ...tening torque of 3 Nm using the mounting holes Requirements for complying with the protection classes For IP68 IP69K all plugs and caps must be properly connected and the tightening torque of 0 6 Nm m...

Page 8: ...52 P071 There is no current limitation to consider because the current for the second device is supplied independently via the auxiliary voltage connection Power supply NOTICE Unwanted voltage dips No...

Page 9: ...2 L coded connector rated 24 V minimum 16 A minimum for all models Cord Listed S SJ SO ST SV or R C AVLV2 marked or specified in UL style page as suitable for external interconnection rated 300 V mini...

Page 10: ...on g n rale les modules BNI pr sentent une bonne r sistance aux produits chimiques et aux huiles En cas d utilisation dans des produits agressifs par exemple produits chimiques huiles lubrifiants et l...

Page 11: ...ion Conditions pr alables au respect des classes de protection Pour IP68 IP69K tous les connecteurs et vis de fermeture doivent tre raccord s correctement et le couple de serrage de 0 6 Nm doit tre re...

Page 12: ...P071 Aucune limitation de courant ne doit tre respect e tant donn que le courant pour le deuxi me appareil est fourni ind pendamment par la connexion de tension auxiliaire Alimentation lectrique ATTE...

Page 13: ...minimum 16 A minimum pour tous les mod les Cordon r pertori S SJ SO ST SV ou R C AVLV2 marqu ou sp cifi dans la page de style UL comme convenant une interconnexion externe d une tension nominale de 30...

Page 14: ...non autorizzati In linea generale i moduli BNI hanno una buona resistenza agli agenti chimici ed agli oli Qualora li si impieghi all interno di fluidi aggressivi ad es prodotti chimici oli lubrifican...

Page 15: ...viti M6 e coppia di serraggio di 3 Nm utilizzando gli appositi fori Presupposti per il rispetto dei gradi di protezione Per i gradi di protezione IP68 IP69K tutti i connettori e tutti i cappucci di ch...

Page 16: ...azione di corrente in quanto tramite il collegamento tensione ausiliaria la corrente per il secondo apparecchio verr erogata in modo indipendente Alimentazione di tensione ATTENZIONE Cadute di tension...

Page 17: ...ato 24 V minimo 16 A minimo per tutti i modelli Cavo Listed S SJ SO ST SV o R C AVLV2 marcato o specificato nella pagina di stile UL come adatto per l interconnessione esterna con un valore nominale m...

Page 18: ...yciem przez osoby niepowo ane Modu y BNI maj zasadniczo dobr odporno na rodki chemiczne i olej W przypadku stosowania rodk w agresywnych np rodk w chemicznych olej w rodk w smarnych ch odz cych zawsze...

Page 19: ...ukcja obs ugi lub dokument Konfiguracja IO Link w witrynie www balluff com na stronie produktu Monta Akcesoria mocuj ce podane s w witrynie www balluff com na stronie produktu Zamocowa modu 2 rubami M...

Page 20: ...nia pr du poniewa przez przy cze napi cia pomocniczego pr d jest udost pniany dla drugiego urz dzenia niezale nie Napi cie zasilaj ce UWAGA Niezamierzone spadki napi cia Nierozdzielone obwody pr du na...

Page 21: ...czone lub okre lone na stronie stylistycznej UL jako odpowiednie do po czenia zewn trznego o napi ciu znamionowym minimum 300 V i przekroju minimum 14 AWG chyba e oznaczono maksymalny pr d obci enia i...

Page 22: ...ngshan Rd 8F Building A Yunding International Commercial Plaza 200125 Pudong Shanghai Phone 86 400 820 0016 Fax 86 400 920 2622 service cn balluff com cn DACH Service Center Germany Balluff GmbH Schur...

Reviews: