background image

 

 

  4

 

N

r./No. 833 340  D/E 

 

 Ausgabe/Edition 0

503

;  Änderungen vo

rbehalten/Subject to modification.

 

 Ersetzt Ausgabe/Replaces edition 0

4

12

 

Setting 

There are two calibration methods: 
 

− 

Standard-Setting: Normal calibration procedure 
(default). This setting is for light-on switching only. 

 

− 

Use Fine Setting only if the standard method does not 
achieve the desired results, i.e., if the distance between 
object and background is very short. Fine setting allows 
both light-on and dark-on switching to be implemented. 
 

Teach in 
 

Standard Setting (for light-on switching only): 
Light-on means the sensor’s output is active as soon as 
the object is detected. 
 
1. Position the background or object you wish to 

suppress. 

2. Press and hold down the SET button until the bi-color 

LED goes out. 

3. Release the SET button and wait until the bi-color LED 

flashes green. The sensor is now ready. 
 

Fine setting (for light-on or dark-on switching): 
Light-on and dark-on require different calibration 
procedures. 
 

A. 

Calibration procedure for light-on: 

1. Position the object you wish to detect. 
2. Press and hold down the SET button until the bi-color 

LED flashes green.  

3. Release the SET button. 
4. Position the background you wish to suppress in the 

beam path.  

5. Press and hold down the SET button until the bi-color 

LED goes out.  

6. Release the SET button. The sensor is now ready. 
 

B.

 Calibration procedure for dark-on: 

Dark-on means the sensor’s output is active as soon as 
no object is detected. 
1. Position the background you wish to suppress in the 

beam path. 

2. Press and hold down the SET button until the bi-color 

LED flashes green. 

3. Release the SET button. 
4. Position the object you wish to detect. 
5. Press and hold down the SET button until the bi-color 

LED goes out. 

6. Release the SET button. The sensor is now ready. 
 
 
 
 
 
 
 
 
 
 
 
 
 

Technical Data 

Optical data 

Operating distance 

70…200 mm 

Output function 

light on or dark on 

Emission type  

red 670 nm 

 
Electrical data 

Operating voltage U

B

 

10...30 V DC 

Ripple 

2 Vpp max. 

Current consumption  
(output current excluded) 

50 mA max. 

Switching output 

PNP or NPN;  
N.O. or N.C  

Output current 

100 mA max. 

Voltage drop 

 2 V 

Reverse polarity protected 

yes 

Short circuit protected 

yes 

Switching frequency 

1 kHz 

Sensitivity setting 

push-button 

Protection class  

 
Mechanical data 

Connection type 

M12, 4 pole connector 

Housing material 

GD-Zn, nickel plated  

Active surface material  

PMMA 

Laser protection class  
DIN EN 60825-1/94 

Vibration 

55 Hz, 1 mm amplitude 

Shock 

30 g, 11 ms 

Dimensions 

50 x 42.5 x 15 mm 

Weight 80 

g. 

 
Time data 

Turn-on delay 

500 

µ

 
Display 

Ready/Error 

Bi-color LED (green/red)

Output function 

yellow LED 

 
Ambient data 

Mechanical protection 

IP67 

Permissible ambient light 

according to  
EN 60947-5-2 

Operating temperature 

-10 … 50 °C 

Storage temperature 

-20 … 70 °C 

 

 

Approvals

 

 

Listed 81U2 IND.CONT.EQ for 
use in the secondary of a class 
2 source of supply 

 

 
 
 
 Balluff 

GmbH 

Schurwaldstrasse 9 
73765 Neuhausen a.d.F. 
Germany 
Phone +49 (0) 71 58/1 73-0 
Fax +49 (0) 71 58/50 10 
E-Mail: balluff@balluff.de 

 www.balluff.com 

Reviews: