IO-Link interface (continued)
6.6.1 Device Access Locks
With this standard parameter, it is possible to activate or
deactivate certain functions of the IO-Link device. With
BTL6-U101-..., there is the option to lock the function of
the parameter manager. To do so, bit 1 of the 2-byte value
must be set to "1" (locked). In order to unlock the
parameter manager, bit 1 is set to "0".
Bit 0
Lock parameter access
(not supported)
Bit 1
Lock parameter management
(supported)
Bit 2
Lock local parameterization
(not supported)
Bit 3
Lock local user interface
(not supported)
Bit 4 to 15 Reserved
Tab. 6-6: Lock parameter data
6.6.2 Profile Characteristic
This parameter indicates which profile is supported by
the IO-Link device.
BTL supports the smart sensor profile with the following
function classes:
– Subindex 1 (Profile Identifier -> DeviceProfileID):
0×0001 (Smart Sensor Profile)
– Subindex 2 (Profile Identifier -> FunctionClassID):
0×8000 (Device Identification Objects)
– Subindex 3 (Profile Identifier -> FunctionClassID):
0×8002 (ProcessDataVariable)
6.6.3 PD Input Descriptor
This parameter describes the composition of the process
data variables used.
Each process data variable can be reached via the
corresponding subindex (subindex 1 for PDV1, subindex 2
for PDV2, etc.).
Each subindex consists of 3 bytes:
– 1st octet: 0x03, data type = signed integer
– 2nd octet: 0x20, data size = 32 bits
– 3rd octet: 0x00, bit offset = 0 (or a multiple of 32)
The complete process data description for all PDVs can be
read out via subindex 0. All blocks of 3 are lined up,
beginning with the description of the highest value PDV.
6.6.4 Application Specific Tag
The
Application Specific Tag
makes it possible to assign
the IO-Link device an arbitrary, max. 32-byte string. This
can only be used for application-specific identification and
applied in the parameter manager. The entire object is
accessed via subindex 0.
6.6.5 Null point offset
Like the process data value, this parameter is a signed
32-bit decimal value. The programmed value must be
within the null and end point in the valid measuring range.
The value is deducted from the actual output value as a
simple offset and therefore shifts the position of the
magnet to an arbitrary point in the measuring range where
the value 0 is output. Access takes place via subindex 0.
The offset value can also be set and deleted via
System
Commands
(see
on page 15).
6.6.6 Event Configuration
All application events can be switched off via the
parameter
Event Configuration
so that they do not have to
be output by the BTL.
To activate or deactivate an event or the
Invalid Bit
function, the corresponding object can be addressed
directly via the subindex and filled with a Boolean value
(True = 0xFF, False = 0x00) (see Tab. 6-7).
Subindex
Event
Subindex 1
Invalid Bit Function
Subindex 2
Position Error
Subindex 3
Position Warning End Point
Subindex 4
Position Warning Nullpoint
Subindex 5
Magnet Change
Tab. 6-7: Event Configuration
The events can also be configured using access via
subindex 0. The last 5 bits are assigned to the sequence
named in Tab. 6-7 and can simply be masked out.
BTL6-U101-M _ _ _ _ -A/B/Y/Z-S4
Magnetostrictive Linear Position Sensor – Rod Style
Summary of Contents for BTL6-U101-M****-A-S4 series
Page 2: ...www balluff com...
Page 3: ...BTL6 U101 M_ _ _ _ A B Y Z S4 Betriebsanleitung deutsch...
Page 4: ...www balluff com...
Page 27: ...BTL6 U101 M_ _ _ _ A B Y Z S4 User s Guide english...
Page 28: ...www balluff com...
Page 51: ...BTL6 U101 M_ _ _ _ A B Y Z S4 Notice d utilisation fran ais...
Page 52: ...www balluff com...
Page 75: ...BTL6 U101 M_ _ _ _ A B Y Z S4 Manuale d uso italiano...
Page 76: ...www balluff com...
Page 99: ...BTL6 U101 M_ _ _ _ A B Y Z S4 Manual de instrucciones espa ol...
Page 100: ...www balluff com...
Page 123: ......