Calibration procedure notes
Prerequisites
– The calibration device is in place or the programming
inputs are connected.
– The transducer is connected to the system controller.
– Voltage or current values from the transducer can be
read (using a multimeter or the system controller).
Values for zero and end point
– Any desired position of the magnet can be used as the
zero or end point. However, the zero and end points
may not be reversed.
– The absolute zero and end points must lie within the
minimum or maximum limits of what can be output
(see value table).
– The distance between the null point and end point
must be at least 4 mm.
The last set values are always saved, regardless
of whether the setting was ended using the
buttons, the programming inputs or
automatically after 10 min. have expired.
Value table for teach-in and adjustment
The following examples refer to transducers
with 0 to 10 V or 4 to 20 mA output.
For all other versions, use the values in the
value table below.
Output
gradient
Linear
transducer
Unit
Min.
value
Null
value
Identification
for adjustment
Identification
for teach-in
End
value
Max.
value
Error
value
Rising
BTL7-A…
V
-
0.5
0
2.0
4.0
+10.0
+10.5
+10.5
BTL7-G…
V
-
10.5
-
10.0
2.0
4.0
+10.0
+10.5
+10.5
BTL7-C…
mA
0
0
6.0
12.0
20.0
20.4
20.4
BTL7-E…
mA
3.6
4.0
6.0
12.0
20.0
20.4
3.6
Falling
BTL7-A…
V
+10.5
+10.0
8.0
6.0
0
-
0.5
-
0.5
BTL7-G…
V
+10.5
+10.0
-
2.0
-
4.0
-
10.0
-
10.5
-
10.5
BTL7-C…
mA
20.4
20.0
14.0
8.0
0
0
20.4
BTL7-E…
mA
20.4
20.0
14.0
8.0
4.0
3.6
3.6
Tab. 6-1: Value table for teach-in and adjustment
Null point
End point
6
Calibration procedure (continued)
BTL7-A/C/E/G_ _ _-M_ _ _ _-A/B/Y/Z(8)-S32/S115/S135/S140/KA_ _/FA_ _