Adjusting (continued)
Displayed values (example)
At 0…10 V
At 4…20 mA
Set end point
►
Bring magnet to the new end point.
9.89 V
19.13 mA
►
Activate
b
for at least 2 s.
> 2 s
b
⇒
The new end point is set with the last valid end
value.
10.00 V
20.00 mA
Adjust end value
►
The end value can be changed using
a
and
b
.
The gradient of the curve changes (see page 15).
10.00 V
20.00 mA
8.00 V
16.80 mA
►
End calibration procedure: Briefly press
a
and
b
simultaneously (< 1 s).
⇒
Set position value is saved.
< 1 s
a
b
2.00 V
6.00 mA
8.00 V
16.80 mA
End adjustment
►
Briefly activate
a
and
b
simultaneously (< 1 s).
< 1 s
a
b
10.50 V
3.60 mA
⇒
The current position value is displayed once the
buttons are released.
7.63 V
18.56 mA
Any of the individual steps for settings can be
selected. The adjustment process can be
ended at any time.
BTL7-A/C/E/G5 _ _ -M _ _ _ _ -H/W(8)-S32/S115/_ _ _
Micropulse Transducer - Rod Style
Summary of Contents for BTL7 Series
Page 1: ...Betriebsanleitung BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 deutsch ...
Page 2: ...www balluff com ...
Page 28: ...User s Guide BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 english ...
Page 29: ...www balluff com ...
Page 55: ...Manual de instrucciones BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 español ...
Page 56: ...www balluff com ...
Page 82: ...Notice d utilisation BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 français ...
Page 83: ...www balluff com ...
Page 109: ...Manuale d uso BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 italiano ...
Page 110: ...www balluff com ...