www.balluff.com
15
english
6
Calibration procedure (continued)
6.3.2 Adjusting
The detailed procedure for adjusting is
The factory set null point and end point is replaced by a
new start point and end point and the associated output
values can be adjusted. The start and end values can be
adjusted as you like up to the limits.
Adjustment is possible from serial number
120615000xxxxx xx onwards.
Steps
►
Move magnet to the new start position.
►
Read new start point by pressing the buttons.
►
Set the new start value by pressing the buttons.
New null point
Before
After
Fig. 6-4: Adjust a new start value
►
Move magnet to the new end position.
►
Read new end point by pressing the buttons.
►
Set the new end value by pressing the buttons.
New end point
Before
After
Fig. 6-5: Adjust a new end value
6.3.3 Reset
Restoring the transducer to its factory settings.
The detailed procedure for the reset is
New start value
New end value
BTL7-A/C/E/G5 _ _ -M _ _ _ _ -H/W(8)-S32/S115/_ _ _
Micropulse Transducer - Rod Style
Summary of Contents for BTL7 Series
Page 1: ...Betriebsanleitung BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 deutsch ...
Page 2: ...www balluff com ...
Page 28: ...User s Guide BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 english ...
Page 29: ...www balluff com ...
Page 55: ...Manual de instrucciones BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 español ...
Page 56: ...www balluff com ...
Page 82: ...Notice d utilisation BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 français ...
Page 83: ...www balluff com ...
Page 109: ...Manuale d uso BTL7 A C E G5_ _ M_ _ _ _ H W 8 S32 S115 _ _ _ S 3 2 italiano ...
Page 110: ...www balluff com ...