www.balluff.com
23
english
8
IO-Link interface: Parameters, commands and events (continued)
8.5
Device specific parameters
Index
(dec)
Name
Subindex
(dec)
Name
Data format
(length)
Access
Value range
Description
Proximity value
0x00B2
(178)
Proximity
0x01 (1) Current analog
UINT16
Proximity value RP in [OHM]
Pin Configuration
0x00BC
(188)
Pin
Function
Selection
0x01 (1) C/Q (PIN 4)
1)
UINT8
RW
0x00 (0) = Sensor Output
(default)
0x01 (1) = Not used.
0x02 (2) = Counter Output
In SIO mode
0x02 (2) DIO (PIN 2)
UINT8
0x00 (0) = Sensor Output
0x01 (1) = Teach-in Input
(default)
0x02 (2) = Counter Output
0x03 (3) = Counter Reset
0x00B4
(180)
Output
Type
0x01 (1) C/Q (PIN 4)
1)
UINT8
RW
0x00 (0) = Disabled
0x01 (1) = PNP
0x02 (2) = NPN
0x03 (3) = Push-Pull (default)
In SIO mode
0x02 (2) DIO (PIN 2)
0x00B5
(181)
Output
Function
0x01 (1) C/Q (PIN 4)
1)
UINT8
RW
0x00 (0) = NO (default)
0x01 (1) = NC
In SIO mode
0x02 (2) DIO (PIN 2)
Counter function / frequency monitor
0x00B6
(182)
Switch
Counter
Settings
0x01 (1) Mode
UINT8
RW
0x00 (0) = Inactive (default)
0x01 (1) = STATIC
0x02 (2) = AUTO
0x03 (3) = SPEED
0x02 (2) Limit
UINT16
0x0000…0xFFFF (0…65535) Counts (0 =
not active,
default)
0x03 (3) Debounce Time
UINT16
0x0000…0xFFFF (0…65535) ms (0 = not
active, default)
0x04 (4) Startup Delay
UINT8
0x00…0xFF (0…255)
s (0 = not
active, default)
0x05 (5) UpperLimit High
UINT16
0x0000…0xFFFF (0…65535) Hz (0 = not
active, default)
0x06 (6) UpperLimit Low
UINT16
0x0000…0xFFFF (0…65535)
0x07 (7) LowerLimit High
UINT16
0x0000…0xFFFF (0…65535)
0x08 (8) LowerLimit Low
UINT16
0x0000…0xFFFF (0…65535)
0x00B7
(183)
Switch
Counter
State
0x01 (1) Status
UINT8
RW
Bit 0: Count limit / Speed ok
Bit 1: Speed too low
Bit 2: Speed too high
0x02 (2) CountValue
UINT16
0x0000…0xFFFF (0…65535) Counts or Hz
0x00BA
(186)
Physical
Input
Debounce
0x00 (0) Physical Input
Debounce
UINT16[]
RW
0x01 (1) PIN Function
(PIN 4/CQ)
UINT16
0 (default) / No input support
0x02 (2) PIN Function
(PIN 2/DIO)
UINT16
300 (Default) / 0…65535 ms
1)
For PIN 4 the setting options are only relevant in SIO mode (in IO-Link mode PIN 4 is automatically responsible for IO-Link communication). The pin configura-
tion can first be changed via IO-Link for then operating the sensor with the new configuration in SIO mode.
Tab. 8-5: Device-specific parameters