Validation type
Whether a connected IO-Link device receives access to the IO-Link master can be con-
trolled using validation.
Configuration options:
Description
0
No validation
1
Allows communication to the IO-Link master only for devices
whose vendor ID (VID) and device ID (DID) correspond to the
configured values.
2
Identical to 1, in addition the serial number of the IO-Link device
is checked.
Vendor ID, VID
Vendor ID for the IO-Link device (refer to the manual for the de-
vice)
Device ID, DID
Device ID for the IO-Link device (refer to the manual for the de-
vice)
Serial Number
(SerNum), optional
Serial number for the IO-Link device (if available; refer to the IO-
Link device's type plate)
Parameter Server
Description
Switched
on
Data management functions enabled, parameter data and identification
data of the IO-Link device are stored permanently.
Switched
off
Data management functions disabled, stored parameter data and identifi-
cation data of the IO-Link device remain stored.
Delete
Data management functions disabled, stored parameter data and identifi-
cation data of the IO-Link device remain stored.
Enable
upload
If only the upload is enabled, the master always starts an upload of the
parameter data. In this case, the upload is independent of the upload flag
of the IO-Link device. If there are no data stored in the master port, an
upload also takes place (e.g. after deleting the data or before the first data
upload).
Enable
download
If only the download is enabled, the master always starts a download of
the parameter data. In this case, the download is likewise independent of
the upload flag of the IO-Link device. If there are no data stored in the
master port, first an upload takes place (e.g. after deleting the data or be-
fore the first data upload).
Enable
upload
and down-
load
If upload and download are enabled, different parameter sets are distin-
guished depending on the upload flag of the IO-Link device. If there are
no parameter data stored in the IO-Link master port, a first upload also
takes place (e.g. after deleting the data or before the first data upload).
If the upload flag is set on the IO-Link device, an upload of the parameter
data takes place.
If no upload flag is set and parameter data has already been stored, a
download of the parameter data always takes place.