TECHNICAL SPECIFICATIONS
MODEL
TBG 80 LX MC
TBG 110 LX MC
TBG 140 LX MC
TBG 200 LX MC
Type-approval PIN
CE-0085BS0067
CE-0085BS0067
CE-0085BS0067
CE-0085BS0067
Maximum natural gas heat power
kW
800
1200
1450
1900
Minimum natural gas heat power
kW
130
180
200
475
¹) natural gas emissions
mg/kWh
Class 3
Class 3
Class 3
Class 3
Operation
Mechanical modulation Mechanical modulation Mechanical modulation Mechanical modulation
50 Hz natural gas transformer
26 kV 40 mA - 230 V 26 kV 40 mA - 230 V 26 kV 40 mA - 230 V 26 kV 40 mA - 230 V
60 Hz natural gas transformer
26 kV 40 mA - 230 V 26 kV 40 mA - 230 V 26 kV 40 mA - 230 V 26 kV 40 mA - 230 V
Maximum natural gas heat rate
Stm³/h
85
127
153
201
Minimum natural gas heat rate
Stm³/h
14
19
21
50
Maximum natural gas pressure
hPa
(mbar)
360
360
360
360
Minimum natural gas pressure
hPa
(mbar)
23
38
36
44
Maximum propane thermal power
kW
800
1200
1450
1900
Minimum propane thermal power
kW
200
180
200
475
Maximum propane thermal flow rate
Stm³/h
32.7
49
59.3
77.7
Minimum propane thermal flow rate
Stm³/h
8.18
7.36
8.2
19.4
Maximum propane pressure
hPa
(mbar)
360
360
360
360
Minimum propane pressure
hPa
(mbar)
45
28
53
42
²)propane emissions
mg/kWh
Class 3
Class 3
Class 3
Class 3
50hz fan motor
kW
1.1
1.5
2.2
3
60hz fan motor
kW
1.1
1.5
2.6
3.5
Absorbed electrical power* 50hz
kW
1.4
2
2.6
3.5
Absorbed electrical power* 60hz
kW
1.4
2
3
4
50 Hz power supply voltage
3N~ 400V ± 10%
3N~ 400V ± 10%
3N~ 400V ± 10%
3N~ 400V ± 10%
60 Hz power supply voltage
3N~ 380V ± 10%
3N~ 380V ± 10%
3N~ 380V ± 10%
3N~ 380V ± 10%
Protection rating
IP44
IP44
IP44
IP44
Flame detection
IONISATION PROBE IONISATION PROBE IONISATION PROBE IONISATION PROBE
Control box
LME 22...
LME 22...
LME 22...
LME 22...
Air flow rate regulation
MECHANICAL CAM
MECHANICAL CAM
MECHANICAL CAM
MECHANICAL CAM
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
75
75.5
83
85
Weight with packaging
kg
88
88
92
95
Weight without packaging
kg
67
67
71
74
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
* Total absorption at start-up with ignition transformer on.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations.
Propane / natural gas CO emissions ≤ 100 mg/kWh
ENGLISH
5 / 34
0006160254_202001
Summary of Contents for TBG 80 LX MC
Page 2: ......
Page 34: ...SCHEMI ELETTRICI ITALIANO 32 34 0006160254_202001...
Page 36: ...ITALIANO 34 34 0006160254_202001...
Page 68: ...WIRING DIAGRAMS ENGLISH 32 34 0006160254_202001...
Page 70: ...ENGLISH 34 34 0006160254_202001...
Page 71: ......