SERVOMOTOR CAMS SQN72.4D5A20 FOR TBG...MC REGULATION
1
2
3
4
I Maximum power air regulation cam (120°)
II Total air closure (burner stopped) (0°)
III Minimum power air regulation cam (10°)
IV Ignition air cam (30°) IV > III
V Ignition transformer cam (40°)*
* Cam V > IV (Approx. 5 - 10°)
1 Motor-camshaft coupling On/Off pin
2 Reference scale
3 Position indicator
4 Adjustable camshaft
Use the corresponding rings to modify the adjustment of the utilized
cams (I - II - III....). The index of the ring indicate on the respective
reference scale the rotation angle taken up for each cam.
ENGLISH
24 / 34
0006160254_202001
Summary of Contents for TBG 80 LX MC
Page 2: ......
Page 34: ...SCHEMI ELETTRICI ITALIANO 32 34 0006160254_202001...
Page 36: ...ITALIANO 34 34 0006160254_202001...
Page 68: ...WIRING DIAGRAMS ENGLISH 32 34 0006160254_202001...
Page 70: ...ENGLISH 34 34 0006160254_202001...