5. Manual Mode 

In Manual Mode, you can leave out the Product 

Probe that Auto Mode requires.  Instead of 
inserting the probe, you program the chiller to chill 
for a certain length of time.  While running in 
manual mode, yet prior to the time ending, it will 
behave as it does when in Auto mode when the 
product probe is above 36°.  After the timer times 

out, it will enter 

Auto holding mode

.  If the 

product probe is plugged in and it its holder, the 
blast chiller will use it as a thermostat set to 36°.  If 
the product probe is not plugged in, it will turn on 
when the air probe reads 45°. 

 

 

The screens in Manual Mode 

Manual Mode

- This indicates the air 

temperature in large letters on the top line, 
followed by the total chill time in small 
letters and the current time (the time since 
the chilling started). 

Measured Temperatures

 - This is screen is 

the same as Auto. 

Manual Mode Time

 –This screen is where 

you set the time for the manual cycle to 
run.  Follow the instructions to adjust the 
time.  Any time changes take effect 
immediately. 

Refrigeration Status

- This is screen is the 

same as Auto. 

Fault Page

- This is screen is the same as 

Auto. 

 
 

6.

 

The Red Light 

The red operational error light and alarm turns on 

when there is a critical failure.  These failures are: 

 

Air temperature above 100°.  If, for some reason, 
the refrigeration should fail, the chiller could 
become extremely hot as the heat comes out of 
the food.  Therefore, if the air temperature reaches 
100°, the controller will shut everything down. 

 

Fan contactor failure - If the fan contactor fails, the 
fans will fail to come on.  The unit will not shut 
down, but it will not be cooling (except for a false 
alarm). 

 

Defrost contactor failure – Same thing here.  
However, you can still use the blast chiller once 
you’re out of Defrost. 

 

Air probe open – The unit cannot operate if the 
controller doesn’t at least have the air temperature 
input.

To get to Manual Mode:

  Push 

F3

 while in Auto.  

You will see the same password entry screen as before.  

After entering the password, push 

F3

 again. 

Summary of Contents for 500

Page 1: ...1 Installation and Operation Manual Northwind Blast Chiller Models 500 and 1000 1 800 24 BALLY Bally Refrigerated Boxes Inc www ballyrefboxes com IM 359 11 2011 Bally Refrigerated Boxes Inc...

Page 2: ...nd parts list and the illustrated plan so that you can complete the installation in a reasonable time without any problems There is also a precise wiring diagram included for any complication and step...

Page 3: ...tep 5 Secure all Panel Sections 8 Step 6 Installation of the Controller 8 Step 7 Installation of Coil Fan Assemblies 9 Step 8 Cable Connections 12 Steps 9 11 Final Assembly 12 Operation Introduction 1...

Page 4: ...4 Note 012993 s are sometimes left out see Chapter 6 3...

Page 5: ...0 Parts List 1 23 Panels 3 2 34 Panel 1 3 Corners 4 4 Ceiling Panels 2 5 36 x 78 Door with electrical junction box complete with twist lock plug wiring 1 6 Control Panel with complete twist lock plug...

Page 6: ...ter to form an interior rectangle which locates the interior blast chiller dimensions 2 Panel Preparation 2 1 Remove all protective paper from panels Leave all special labels on the skins 2 2 During t...

Page 7: ...nt crews have installed boxes upside down Panel assembly sequence of a Northwind 500 The Coil Frame Assembly is installed in the box before the door is added since the coil is taller than the opening...

Page 8: ...back wall Do not fully lock 4 4 Caulk the groove or tongue of the rear ceiling panel and the rest of the wall tongue area 4 5 Bring up the front ceiling panel and lock it to the back ceiling panel fu...

Page 9: ...slot in the front of the box Then push the rectangular collar of the control assembly into the slot until the base of the controller is against the face of the blast chiller Back out the three screws...

Page 10: ...he coil frame into the appropriate side 3 Center the frame within 1 16 between the two walls 4 Install screws into the rear top back brace This will force the frame against the wall permanently 5 Rein...

Page 11: ...lace the Top Fan Trim Piece between the same front cover and the frame 7 4 Installing the Condensate Drain 1 A tube must be installed to drain condensate from each coil assembly 2 Find the pan which i...

Page 12: ...ll on a NW1000 and rear walls You will find screw holes in the walls from our initial assembly Use these first Plenum Installation The plenum is installed with the electrical plug toward the coil fram...

Page 13: ...s done in good practice according to local code Coils arrive with a holding pressure of 60 psi nitrogen 11 Setting the Ceiling Plenum The ceiling plenum can now be set in place plugged in and mounted...

Page 14: ...cording to the color code set for them Also inspect all of the external wiring making sure that all the wiring is correct according to the wiring specifications included Now that your Bally Northwind...

Page 15: ...allow you to monitor two other food locations The auxiliary probes are not necessary for proper functioning of the blast chiller 3 Operating the Blast Chiller 3 1 Automatic The normal or default proce...

Page 16: ...nown to occur Refrigeration Status This is an on off indicator There is sometimes an explanation for a certain refrigeration state for instance if you start the auto mode then open and close the door...

Page 17: ...heaters in the coils will turn on and heat the coil They will stay on even if the door is opened The Defrost cycle ends one of two ways either by a 20 minute timer ending or by the Defrost Termination...

Page 18: ...e time for the manual cycle to run Follow the instructions to adjust the time Any time changes take effect immediately Refrigeration Status This is screen is the same as Auto Fault Page This is screen...

Page 19: ...or is at room temperature and stay in defrost the full 20 minutes See the above information to replace it if you experience either situation Item Bally PN Location Means of Access Fan Motor 016915 Ins...

Page 20: ...20 A Northwind 500 Model is shown A Northwind 1000 Model is twice as deep with only one controller...

Reviews: