Installation manual phase inverter (16/32A)
(08.2016)
19 / 28
7. The terminals are open at the time of delivery. Guide the bare individual conductors into the
opening (6) and tighten the screws (5) with a torque of at least 0.8 Nm. Take care to ensure
that only the bare individual conductor (without insulation) is clamped. Pay attention to the
marking of the terminals and ensure that the assignment of the individual conductors to the
terminals is correct.
8. Check whether the individual conductors are seated tightly by pulling them lightly. If this is not
the case, open the terminal and repeat the previous step.
9. For wall-mounted device connectors: Tighten the cable gland.
10. Fix the housing with the panel mounting appliance (panel mounting variant) or fix the cover
with screws to the housing (surface-mounting variants). NOTICE! With the panel mounting
variants, make sure that you insert the gasket, and with the surface-mounting variants, that
the insert with the connections is placed correctly into the bottom part of the housing!