background image

FAN BELT ADJUSTMENT
Some of the smaller axial fan models use individual V-
belts, but most of the models use multi-groove, banded
belts. Belt tension should be checked and adjusted
(as needed) every month. 
To properly adjust the belt
tension, position the fan motor so that moderate pressure
on the belt midway between the sheaves will produce 1/2”
deflection in centrifugal fan units and the deflection shown
in Table 4 below for axial fan units. The position of the fan
motor can easily be changed by adjusting the rod which
extends from the frame to the motor base.

1. Loosen the locking nut (See Figure 5, 5a, 5b)

2. Rotate the adjusting nut

a. To loosen belt tension, turn clockwise (on models

VTL, VFL and VCL turn counterclockwise).

b. To tighten belt tension, turn counterclockwise (on

models VTL, VFL and VCL turn clockwise).

3

Tighten the locking nut – failure to do so may result in
the motor base vibrating free, hence, loosening the
belt tension.

Note: There should be no “chirp” or “squeal” when the fan
motor is started.

Figure 6 – Checking Sheave Alignment

HINGE

ADJUSTING
SCREW

Figure 5B – Adjustable Motor Base
VC2-319-1774

DEFLECTION

(inches)

MODEL NO.

VC2-N138-N191

VC2-N206-N235

VC2-N261-N301

VC2-N356-N446

VC2-319-1774

9/16

"

11/16

"

11/16

"

13/16

"

13/16

"

FAN DRIVES

The drive alignment should be checked annually to
ensure maximum belt life. 
This can be done by placing
a straightedge across both sheaves as shown in Figure 6.
When the drive is properly aligned, the straightedge will
contact all four points as indicated. If realignment is nec-
essary, loosen the motor sheave and align it with the fan
sheave. Allow approximately 1/4” for draw-up as the
motor sheave is pulled tight on the bushing, then retighten
the bushing screw:

FAN

SHEAVE

MOTOR

SHEAVE

POINT OF CONTACT

STRAIGHTEDGE

MOTOR REPLACEMENT
On rare occasions, the fan motor will have to be replaced.
On the VC2 models, make sure the drain holes are point-
ing in the downward direction. This may require that the
end bell be reversed on some motors.

SPRAY NOZZLES AND HEAT TRANSFER SECTION

The spray nozzles and heat transfer section should
be inspected and cleaned each month. 
The inspection
procedure is as follows:

1. Shut off the fan, but leave the pump running.

2. Remove the eliminators.

3. Check to see if the nozzles are producing the spray

pattern shown in Figure 7a for cooling towers or 7b for
coil products.

4. Clean any nozzles which are clogged. If necessary,

the nozzle and rubber grommet may be removed for
cleaning.

5. Inspect the coil or wet deck surface. Any corrosion,

damage, or obstructions must be corrected.

6. Some VF1, VFL, VC1, VC2, and VCL units are provid-

ed with an extended surface finned coil. During the win-
ter season, when the ambient temperature is well
below design, units with this coil can operate with the
spray pump off. The coil is designed for seasonal dry
operation followed by seasonal wet operation, and 

not

for frequent cycling of the spray pump. Frequent spray
pump cycling may lead to excessive scale buildup.

Caution: Do not use steam or high pressure water to
clean cooling tower wet deck surface of materials
other than steel.

11

TABLE 4. Fan Belt Deflection for VC2 Models

Summary of Contents for V Series

Page 1: ...inspection and service identi fied A copy of the unit certified drawing should also be available for reference If you need additional informa tion about the operation or maintenance of this equip men...

Page 2: ...87 Baltimore Aircoil Company 2 Basin Section CASING WET DECK SURFACE SPRAY NOZZLES SPRAY BRANCHES SPRAY HEADER ELIMINATORS FAN DISCHARGE COWLS HEAVY DUTY CONSTR WATER MAKE UP VALVE ADJUSTABLE FLOAT AC...

Page 3: ...CONDENSERS Heat Transfer Coil Section Basin Section 3 CASING COIL SPRAY NOZZLES SPRAY NOZZLES ELIMINATORS FAN DISCHARGE COWL WATER MAKE UP VALVE ASSEMBLY ADJUSTABLE FLOAT ACCESS DOOR STRAINER WATER P...

Page 4: ...D BASIN SECTION FOR VC2 319 1774 PROTECTION FROM MOVING PARTS TWO STAGE AXIAL FLOW FAN FAN SCREEN FAN SHAFT FAN BALL BEARING FAN DRIVES FAN MOTOR WATER MAKE UP VALVE ASSEMBLY STRAINER WATER BLEED SPRA...

Page 5: ...EVAPORATIVE CONDENSERS ELIMINATORS WATER DISTRIBUTION SYSTEM AIR INLET RING FAN SHAFT AND BEARING FAN FAN MOTOR STRAINER ASSEMBLY WATER MAKEUP VALVE WET DECK SURFACE SPRAY NOZZLES ELIMINATORS COIL FA...

Page 6: ...the protection of authorized ser vice and maintenance personnel each fan and pump motor associated with this equipment must be installed with a lockable disconnect switch located within sight of the c...

Page 7: ...essure greater than 10 0 psig may cause damage to the distribution system 12 Inspect the spray nozzles and heat transfer section 13 Start the fan and check for the proper rotation as indi cated by the...

Page 8: ...e or for remote sump application It is located inside the unit cold water basin within easy reach from the access door at the connection end of each unit The standard make up assembly see Figure 1 con...

Page 9: ...2 each equipped with a lubrication fitting and locking collar Models VTO 65 to 116 VF1 027 VF1 036 and VC1 72 thru 135 also have a sleeve bearing see Figure 3 located midway on the shaft The fan shaf...

Page 10: ...tion while holding the shaft 3 Retighten the set screw ADJUSTABLE MOTOR BASE The motor base slides and adjusting screw See Figure 5 should be coated twice a year using a good quality corro sion inhibi...

Page 11: ...ct all four points as indicated If realignment is nec essary loosen the motor sheave and align it with the fan sheave Allow approximately 1 4 for draw up as the motor sheave is pulled tight on the bus...

Page 12: ...ich do not require extraordinary corrosion protection can be touched up with a repair kit B A C Part No 16 133P In the unlikely event that the damage is more extensive than simple scratches or dents c...

Page 13: ...ntrol to determine whether any critical speeds may be encountered and if any motor modifi cations may be required Recommended Operating Speeds For optimum system performance and equipment longevity fa...

Page 14: ...tment CORROSION AND SCALE CONTROL In Evaporative Cooling Products cooling is accomplished by the evaporation of a portion of the process water as it flows through the unit As this water evaporates the...

Page 15: ...trations of iodine through the make up water line the IOBIO Control automatically controls unwanted microbiological contami nants in the open water system Contact your local B A C Representative for m...

Page 16: ...ltimore Aircoil P O Box 7322 Baltimore Maryland 21227 410 799 6200 Fax 410 799 6416 www BaltimoreAircoil com email info BaltimoreAircoil com SEN 10M 09 00 Printed on Recycled Paper Printed in the U S...

Reviews: