background image

Maintenance

Procedures

(continued)

9

As an option, an electric water level control package is
available in lieu of the above described mechanical make-
up assembly. The package consists of a probe-type liquid
level control assembly and a slow closing solenoid valve.
Stainless steel electrodes, factory set at predetermined
lengths, extend from a NEMA 4 electrode holder into the
cold water basin. These electrodes should be periodi-
cally wiped clean to prevent accumulations of scale,
corrosion, sludge or biological growth from interfer-
ing with the electrical circuit. 
With the electric water
level control package, the water level is maintained at the
recommended operating level regardless of the system
thermal load. Therefore, it is not necessary, nor is it rec-
ommended that the operating level be adjusted. During
initial and seasonal start-up, the probe-type level control
assembly should be bypassed to fill the cold water basin
to approximately 1/2” below the overflow connection.

Unit operation at the recommended water level will

ensure that the unit basin contains sufficient water volume
to prevent air entrainment in the circulating pump during
system start-up and to provide sufficient excess basin
capacity to accept the total system pull-down volume. The
“total system pull-down volume” is the quantity of water
suspended in the tower during pump operation plus that
contained in the water distribution system, external piping,
and any heat exchangers which could drain to the tower
cold water basin when the circulating pump is shut down.

FAN SHAFT BEARINGS
The fan shafts on VTO, VT1, VTL, VF1, VFL, VC1, and
VCL units are supported at each end by ball bearings (see
Figure 2), each equipped with a lubrication fitting and
locking collar. Models VTO-65 to 116, VF1-027, VF1-036,
and VC1-72 thru 135 also have a sleeve bearing (see
Figure 3) located midway on the shaft. 

The fan shafts on VC2 units are supported by ball bear-

ings (see Figure 2A) in the middle of the shaft with fans at
each end. Each bearing is equipped with a lubrication fit-
ting and locking collar. Lubrication lines are extended to
the outside of the unit as standard.

Ball Bearings
Under normal operating conditions, the bearings should
be greased every 2,000 operating hours or at least every
six months. The bearings should also be greased at sea-
sonal start-up and shut-down. Only lubricate the bearings
with one of the following water resistant inhibited greases
which are good for ambient temperatures ranging from
–65°F to 250°F:

American – Rycon Premium #3

Exxon – Beacon #325

Shell – Aeroshell #7

Mobil – Mobilgrease #28

Chevron – SRI #3

Keystone – 84 EP Light

Only lubricate the bearings with a hand grease gun.

Do not use high pressure grease guns since they may
rupture the bearing seals. 
When lubricating, purge the
old grease from the bearing by gradually adding grease
until a bead of new grease appears at the seal.

Sleeve Bearings
Prior to start-up and during the first week of operation, the
bearing oil cup must be refilled with an industrial-type min-
eral oil (see Table 3) to saturate the felt wick in the bear-
ing reservoir. After the initial start-up, fill the bearing oil
cup every 1,000 operating hours or at least every six
months. When ambient temperatures below 0°F are
expected, a light oil must be used. With such light oils, the
bearing oil cup should be checked and refilled several
times during the first several hours of operation until the
bearings reach operating temperature.

LUBE

FITTING

LOCKING

COLLAR

Figure 2 – Ball Bearing

LUBE FITTING

LOCKING COLLAR

Figure 2A – Ball Bearing

Summary of Contents for V Series

Page 1: ...inspection and service identi fied A copy of the unit certified drawing should also be available for reference If you need additional informa tion about the operation or maintenance of this equip men...

Page 2: ...87 Baltimore Aircoil Company 2 Basin Section CASING WET DECK SURFACE SPRAY NOZZLES SPRAY BRANCHES SPRAY HEADER ELIMINATORS FAN DISCHARGE COWLS HEAVY DUTY CONSTR WATER MAKE UP VALVE ADJUSTABLE FLOAT AC...

Page 3: ...CONDENSERS Heat Transfer Coil Section Basin Section 3 CASING COIL SPRAY NOZZLES SPRAY NOZZLES ELIMINATORS FAN DISCHARGE COWL WATER MAKE UP VALVE ASSEMBLY ADJUSTABLE FLOAT ACCESS DOOR STRAINER WATER P...

Page 4: ...D BASIN SECTION FOR VC2 319 1774 PROTECTION FROM MOVING PARTS TWO STAGE AXIAL FLOW FAN FAN SCREEN FAN SHAFT FAN BALL BEARING FAN DRIVES FAN MOTOR WATER MAKE UP VALVE ASSEMBLY STRAINER WATER BLEED SPRA...

Page 5: ...EVAPORATIVE CONDENSERS ELIMINATORS WATER DISTRIBUTION SYSTEM AIR INLET RING FAN SHAFT AND BEARING FAN FAN MOTOR STRAINER ASSEMBLY WATER MAKEUP VALVE WET DECK SURFACE SPRAY NOZZLES ELIMINATORS COIL FA...

Page 6: ...the protection of authorized ser vice and maintenance personnel each fan and pump motor associated with this equipment must be installed with a lockable disconnect switch located within sight of the c...

Page 7: ...essure greater than 10 0 psig may cause damage to the distribution system 12 Inspect the spray nozzles and heat transfer section 13 Start the fan and check for the proper rotation as indi cated by the...

Page 8: ...e or for remote sump application It is located inside the unit cold water basin within easy reach from the access door at the connection end of each unit The standard make up assembly see Figure 1 con...

Page 9: ...2 each equipped with a lubrication fitting and locking collar Models VTO 65 to 116 VF1 027 VF1 036 and VC1 72 thru 135 also have a sleeve bearing see Figure 3 located midway on the shaft The fan shaf...

Page 10: ...tion while holding the shaft 3 Retighten the set screw ADJUSTABLE MOTOR BASE The motor base slides and adjusting screw See Figure 5 should be coated twice a year using a good quality corro sion inhibi...

Page 11: ...ct all four points as indicated If realignment is nec essary loosen the motor sheave and align it with the fan sheave Allow approximately 1 4 for draw up as the motor sheave is pulled tight on the bus...

Page 12: ...ich do not require extraordinary corrosion protection can be touched up with a repair kit B A C Part No 16 133P In the unlikely event that the damage is more extensive than simple scratches or dents c...

Page 13: ...ntrol to determine whether any critical speeds may be encountered and if any motor modifi cations may be required Recommended Operating Speeds For optimum system performance and equipment longevity fa...

Page 14: ...tment CORROSION AND SCALE CONTROL In Evaporative Cooling Products cooling is accomplished by the evaporation of a portion of the process water as it flows through the unit As this water evaporates the...

Page 15: ...trations of iodine through the make up water line the IOBIO Control automatically controls unwanted microbiological contami nants in the open water system Contact your local B A C Representative for m...

Page 16: ...ltimore Aircoil P O Box 7322 Baltimore Maryland 21227 410 799 6200 Fax 410 799 6416 www BaltimoreAircoil com email info BaltimoreAircoil com SEN 10M 09 00 Printed on Recycled Paper Printed in the U S...

Reviews: