ENGLISH
14 / 32
0006081530_201711
SUPPLY LINE
The figure below shows the gas supply line block diagram.
The gas train is certified in compliance with EN 676 Standard and
supplied separately from the burner.
DANGER / ATTENTION
Install a manual shut-off valve and a vibration-proof joint
upstream of the gas valve, according to the layout shown in
the block diagram.
GAS TRAIN BLOCK DIAGRAM
M
M
12
10
9
14
11
13
8
4
7
6
5
3
2
1
0002910950N2
TO BE CARRIED OUT BY THE INSTALLER
GAS TRAIN SUPPLIED BY THE MANUFACTURER
1
Manual shut-off valve
2
Vibration-proof joint
3
Gas filter
4
Minimum gas pressure switch and for controlling gas leaks
5
Safety valve
6
Pressure regulator
7
Valve seal control device (mandatory for burners with maximum
rated heating capacity higher than 1200kW)
8
Working valve
9
Air regulation servomotor
10
Air regulation damper
11
Air pressure switch
12
Combustion head
13
Gas throttle valve
14
Gas regulation servomotor