ENGLISH
33 / 44
0006160028_201510
MAINTENANCE TIME
COMBUSTION HEAD
GAS
DIESEL
ELECTRODES
VISUAL INSPECTION OF THE INTEGRITY OF CERAMICS. TIP GRIN-
DING, CHECK DISTANCE, CHECK ELECTRICAL CONNECTION.
YEARLY
YEARLY
FLAME DISK
INTEGRITY VISUAL INSPECTION FOR POSSIBLE WARPING, CLEA-
NING
YEARLY
YEARLY
COMBUSTION HEAD COMPONENTS
INTEGRITY VISUAL INSPECTION FOR POSSIBLE WARPING, CLEA-
NING
YEARLY
YEARLY
LIQUID FUEL NOZZLES
REPLACEMENT
N.A.
YEARLY
INSULATING SEAL
VISUAL INSPECTION OF LEAK TIGHTNESS AND POSSIBLE REPLA-
CEMENT
YEARLY
YEARLY
AIR LINE
GAS
DIESEL
AIR SHUTTER BEARINGS
GREASING, (NOTE: apply only to burners with bearings to be greased) 6 MONTHS 6 MONTHS
AIR FAN
CLEANING
YEAR
YEAR
AIR PRESSURE SWITCH
CLEANING
YEAR
YEAR
AIR PRESSURE PIPES AND OUTLET
CLEANING
YEAR
YEAR
SAFETY COMPONENTS
GAS
DIESEL
FLAME SENSOR
CLEANING
YEAR
YEAR
GAS PRESSURE SWITCH
OPERATIONAL TEST
YEAR
YEAR
VARIOUS COMPONENTS
GAS
DIESEL
ELECTRIC MOTORS (BEARINGS/COO-
LING FAN)
CLEANING, (see if the supplier's indications were provided)
YEAR
YEAR
LEVERS/STRAP SYSTEM/BALL JOINTS
(BACKLASH/LUBRICATION)
CHECK FOR POSSIBLE BACKLASH
YEAR
YEAR
HOSES
REPLACEMENT
N.A.
5 YEARS
FUEL LINE
GAS
DIESEL
PUMP FILTER
CLEANING
YEAR
YEAR
LINE FILTER
CLEANING/REPLACEMENT (SPARE CARTRIDGE?)
YEAR
YEAR
GAS FILTER
REPLACE THE FILTER
YEAR
YEAR
COMBUSTION PARAMETERS
GAS
DIESEL
CO TEST
COMPARISON WITH THE VALUES RECORDED UPON THE EQUIP-
MENT START-UP
YEAR
YEAR
CO2 TEST
COMPARISON WITH THE VALUES RECORDED UPON THE EQUIP-
MENT START-UP
YEAR
YEAR
TEST OF FUMES ACCORDING TO
BACHARACH INDEXES
COMPARISON WITH THE VALUES RECORDED UPON THE EQUIP-
MENT START-UP
YEAR
YEAR
NOX TEST
COMPARISON WITH THE VALUES RECORDED UPON THE EQUIP-
MENT START-UP
YEAR
YEAR
IONISATION CURRENT TEST
COMPARISON WITH THE VALUES RECORDED UPON THE EQUIP-
MENT START-UP
YEAR
YEAR
FUME TEMPERATURE TESTING
COMPARISON WITH THE VALUES RECORDED UPON THE EQUIP-
MENT START-UP
YEAR
YEAR
GAS PRESSURE REGULATOR
PRESSURE MEASUREMENT UPON START-UP
YEAR
N.A.
IMPORTANT
In case of heavy use or particular fuels, the maintenance frequency must be increased and adapted to the use conditions according
to the maintenance technician's indications.
Summary of Contents for 56460010
Page 2: ......
Page 40: ...SCHEMI ELETTRICI ITALIANO 38 44 0006160028_201510...
Page 41: ...ITALIANO 39 44 0006160028_201510...
Page 42: ...ITALIANO 40 44 0006160028_201510...
Page 43: ...ITALIANO 41 44 0006160028_201510...
Page 44: ...BT1 BA BP I1 I2 I3 I4 ITALIANO 42 44 0006160028_201510...
Page 46: ...ITALIANO 44 44 0006160028_201510...
Page 84: ...ENGLISH 38 44 0006160028_201510 WIRING DIAGRAMS...
Page 85: ...ENGLISH 39 44 0006160028_201510...
Page 86: ...ENGLISH 40 44 0006160028_201510...
Page 87: ...ENGLISH 41 44 0006160028_201510...
Page 88: ...ENGLISH 42 44 0006160028_201510 BT1 BA BP I1 I2 I3 I4...
Page 90: ...ENGLISH 44 44 0006160028_201510...
Page 91: ......