DUNGS VALVE

MODEL MB-ZRDLE...B01 AND B02

The monobloc DUNGS Model MB-ZRDLE is made up of:
a) Minimum gas pressure switch (3) and maximum gas pressure (12)
b) Gas filter (6)
c) Pressure regulator (stabilizer) (2) (only for version B01)
d) Safety valve (incorporated in the pressure regulator) which opens and closes rapidly (4)
e) Principle valve with two positions (1st flame and 2nd flame) which opens slowly with an adjustable initial rapid

release and rapid closing (8).

Before proceeding with regulation, read the following:
1) It is possible to reach the gas filter (6) in order to clean it, by removing one of the two side closing plates.
2) The pressure stabilizer can be regulated from 40 to 200 mm.W.C. by manoeuvring its regulating screw. It can be

reached by sliding the cover (2) to one side. The and viceversa is about 60 turns. Do not force against the end-of-
the-run position. Before starting up the burner, give the screw at least 15 turns towards the + sign. Around the
screw are arrows with symbols which indicate the sense of rotation to increase the pressure (in a clockwise
direction) and the sense of rotation to decrease pressure (in an anti-clockwise direction).

The stabilizer hermetically closes from “upstream” to “downstream” when there is no gas flow. Different  springs to

obtain different pressure values form those described above are not foreseen.

To regulate the pressure stabilizer, connect a water manometer to the rubber tube holder installed on the valve, to

tap Pa (7), in correspondence with the stabilizer exit.

3) It is not necessary to regulate the rapid opening and closing safety valve (4).
4) Principle valve (8).
Regulating the initial rapid release effects the 1st and 2nd opening positions of the valve.
Regulation of the rapid release and of the hydraulic brake modify the 1st and 2nd positions of the valve in proportion
to the output regulated. To carry out regulation, unscrew the protection cover (11) and use the back part of it as a tool
to turn the pin.
Rotation in a clockwise direction

= minor rapid release

Rotation in an anti-clockwise direction = greater rapid release

REGULATING THE FIRST POSITION (1ST FLAME)

Loosen the screw with the protruding cylindrical head (1)
Give the knob (10), which regulates the output for the 2nd flame, at least one turn in the direction of the arrow which
indicates the + sign (anti-clockwise direction).

ATTENTION:

 If this knob which regulates the 2nd flame is not given at least one turn towards the + sign, the valve will

not open in the 1st position.

Rotate the regulating ring (9) of the 1st flame in the direction indicated by the arrow towards the + sign (anti-clockwise
direction). As an indication, this should be a little more than two turns from the end-of-the-run position.
Then, when the 1st flame only is alight, rotate adequately ring (9) in order to obtain the gas delivery desired.
The complete run of the output regulator, from the - position to the + position, and viceversa, is about three and a half
turns. Rotation of the regulator in a clockwise direction, determines a reduction in delivery; rotation in an anticlockwise
direction increase delivery.

REGULATING THE SECOND POSITION (2ST FLAME)

Loosen the screw with the protruding cylindrical head (1)
Rotate the knob (10) in the direction indicated by the arrow for the + sign (anti-clockwise direction) as considered
necessary in order to obtain the gas delivery required for the 2nd flame. The complete run of the regulator from the -
position to the + position, and viceversa, is about FIVE turns. Rotate in a clockwise direction to determine a reduction
in delivery and in an anti-clockwise direction to increase it. After regulating the gas delivery for the 1st and 2nd
flame,remember to tighten home the screw (1) to avoid the regulatormoving out of the position at which it has been set.

N° 0002910310

Rev. 26/09/97

1st POSITION

2nd POSITION

DETAILS OF TERMINAL BOARD

FOR VALVE MB-ZRDLE...

VALVE

INLET MAX PRESSURE

ADJUSTTABLE OUTLET PRESSURE

TYPE OF GAS

MODEL

 (PE) mbar

FROM THE STABILIZER (PA) mbar

MB ...B01 S 20

200

from 4 to 20

Gas maturale

MB ... B01 S 50

360

from 4 to 50

L.P.G

MB ... B02

360

L.P.G.

Summary of Contents for BGN 34 P

Page 1: ...instrucciones antes de poner en funcionamento los quemadores y efectuar las tareas de mantenimiento Los trabajos que se efect en al quemador y a la instalaci n deben ser efectuados s lamente por perso...

Page 2: ...ada por la BALTUR misma y con los accesorios de linea gas certificados CE suministrables a pedido NOTA la presente declaraci n no tiene validez respecto a la Norma CE o UNI para los quemadores de gas...

Page 3: ...pane L P G 33 Layout diagram with vaporisation 61 Air regulation servomotor 62 Electric diagram 64 NDICE P GINA Caracteristicas tecnicas 6 Aplicaci n del quemador a al caldera 35 Conexiones el ctricas...

Page 4: ...ericolose come la formazione di miscele tossiche ed esplosive Per chiarire meglio la situazione facciamo un esempio Per bruciare correttamente una quantit di combustibile corrispondente alla modesta p...

Page 5: ...to periodo chiudere il rubinetto o i rubinetti di alimentazione del combustibile Avvertenze particolari per l uso del gas Far verificare da personale professionalmente qualificato a che la linea di ad...

Page 6: ...ESSIONE PRESSURE PRESSION DRUCK PRESION 19 MIN mbar 30 mbar MIN 30 MOTORE MOTOR MOTEUR MOTOR CARATTERISTICHE TECNICHE TECHNICAL DATA CACTERISTIQUES TECHNIQUES TECNISCHEN DATEN CARACTERISTICAS TECNICAS...

Page 7: ...upporto morsettiera 7 Terminal board support 8 Motore ventola 8 Fan motor 9 Monoblocco 9 Monobloc 10 Flangia scorrevole 10 Sliding flange 11 Guarnizione 11 Gasket 12 Testa di combustione 12 Combustion...

Page 8: ...gulaci n de aire 4 Luftklappenstellmotor 5 Pulsador de desbloqueo 5 Entriegelungsknopf 6 Dispositivo 6 Feuerungsautomat 7 Soporte tablero de bornes 7 Klemmenhalterung 8 Motor impulsor 8 L ftermotor 9...

Page 9: ...questa tubazione in prossimit del bruciatore un raccordo adatto per consentire un agevole smontaggio del bruciatore e o l apertura del portellone della caldaia La valvola gas DUNGS mod MB incorpora fi...

Page 10: ...finestre aperte effettuare lo spurgo dell aria contenuta nella tubazione Occorre aprire il raccordo sulla tubazione in prossimit del bruciatore e successivamente aprire un poco il o i rubinetti di in...

Page 11: ...rometro 5 Con bruciatore acceso adeguare l erogazione al valore desiderato per la prima fiamma Metano 8550 kcal m3 effettuando la lettura al contatore Detta portata pu essere modificata agendo sull ap...

Page 12: ...one praticamente indispensabile quando il bruciatore lavora su focolare pressurizzato e o ad alto carico termico Da quanto sopra esposto risulta evidente che il dispositivo che chiude l aria sulla tes...

Page 13: ...SPOSIZIONE DISCO ELETTRODI E REGOLAZIONE TESTA DI COMBUSTIONE Testa di combustione Miscelatore Elettrodo ionizzazione Elettrodo accensione Pomello di comando e fissaggio testa di combustione spostare...

Page 14: ...x 3 ripetizioni O cellula UV tipo QRA LMG25 330B27 2 5 30 3 2 2 8 5 Max 3 ripetizioni Con AGQ2 A27 LMG25 350B27 2 5 30 5 4 2 10 5 Max 3 ripetizioni Legenda tw Tempo di attesa t4 Intervallo tra Fine TS...

Page 15: ...za con programma completo Presenza prematura del segnale di fiamma durante t1 Blocco Contatto del pressostato aria LP incollato in posizione di lavo ro nessun avviamento e blocco dopo 65 s Contatto de...

Page 16: ...rante il funzionamento LMG25 Anomalia dei contatti in uscita Errore nelle connessioni elettriche Tensione anomala ai morsetti in uscita Errore interno dell apparecchiatura di controllo fiamma Durante...

Page 17: ...17...

Page 18: ...to gas minima 4 Valvola di sicurezza 5 Presa di pressione ingresso gas 6 Filtro 7 Presa di pressione dopo lo stabilizzatore di pressione Pa 8 Valvola principale l e 2 fiamma 9 Anello regolazione eroga...

Page 19: ...ne 11 e usare la sua parte posteriore come attrezzo per far ruotare il perno Rotazione oraria scatto rapido minore Rotazione antioraria scatto rapido maggiore REGOLAZIONE PRIMA POSIZIONE 1 FIAMMA Alle...

Page 20: ...re almeno un terzo della superficie complessiva deve essere posta nella parte inferiore di parete esterna a filo pavimento 3 Esecuzioni dell impianto del gas liquido per assicurare corretto funzioname...

Page 21: ...21 SCHEMA DI PRINCIPIO PER RIDUZIONE PRESSIONE GPL A DUE SALTI PER BRUCIATORE OPPURE PER CALDAIA N BT 8721 2 Rev 21 03 90 8721 2 pcx...

Page 22: ...to install a suitable pipe union in the pipeline in proximity to the burner to allow for easy disassembly of the burner and opening of the boiler door The DUNGS mod MB valve incorporates a filter and...

Page 23: ...nection nearest to the burner and then open the gas cut off cocks a little Way until there is the characteristic smell of gas and then shut off the cock Wait for an appropriate time according to the p...

Page 24: ...t set the delivery rate to the first flame to the desired level methane 8550 kcal m3 making the reading on the counter This rate can be changed by adjusting the regulator on the valve as illustrated a...

Page 25: ...is condition is practically indispensable when the burner is working on a pressurized boiler and or a high thermic load It is clear from the above description that the device that closes the air to th...

Page 26: ...TION AIR REGULATION PRINCIPLE DIAGRAM FOR GAS BURNERS N BT 9372 1 Combustion head Mixer Ionization electrode Ignition electrode Driving knob and combustion head fixing phus forwards order to open the...

Page 27: ...27...

Page 28: ...28...

Page 29: ...29...

Page 30: ...30...

Page 31: ...re switch minimum 4 Safety valve 5 Pressure tap at gas entry 6 Filter 7 Pressure tap after pressure stabilizer Pa 8 Principle valve 1st and 2nd flame 9 Regulating ring 1st flame delivery 10 Regulating...

Page 32: ...as a tool to turn the pin Rotation in a clockwise direction minor rapid release Rotation in an anti clockwise direction greater rapid release REGULATING THE FIRST POSITION 1ST FLAME Loosen the screw w...

Page 33: ...nd a minimum of 0 5 m2 At least one third of the entire surface of these inlets must be located in the lower part of the external wall flush with the floor 3 Requirements for liquid gas plant to ensur...

Page 34: ...34 GENERAL DIAGRAM FOR TWO STAGE L P G PRESSURE REDUCTION FOR BURNER OR BOILER N BT 8721 2GB Rev 21 03 90...

Page 35: ...del folleto y tiene que ser totalmente herm tica y haber sido probada antes de la prueba de ensayo del quemador Es indispensable instalar en esta tuber a cerca del quemador un racor adecuado para perm...

Page 36: ...taci n del motor sea correcto Es indispensable si no se ha hecho ya en el momento de la conexi n del quemador a la tuber a del gas con la mayor cautela y con las puertas y ventanas abiertas efectuar l...

Page 37: ...al circuito de ionizaci n Precisamos que el hilo con alto aislamiento que proviene del electrodo tiene que ser conectado al negativo signo del micro amper metro 5 Con el quemador encendido adecuar el...

Page 38: ...saciones de llama esto es pr cticamente indispensable cuando el quemador trabaja con un hogar presurizado y o con una alta carga t rmica Con lo expuesto hasta ahora resulta evidente que el dispositivo...

Page 39: ...BT 9372 1 DISPOSICI N DISCO ELECTRODOS Y REGULACI N CABEZA DE COMBUSTI N Pomo de mando y sujeci n cabeza de combusti n desplazar atr s para abrir el paso de aire entre disco y cabeza desplazar adelant...

Page 40: ...40...

Page 41: ...41...

Page 42: ...42...

Page 43: ...43...

Page 44: ...s m nima 4 V lvula de seguridad 5 Toma de presi n entrada gas 6 Filtro 7 Toma de presi n despu s del estabilizador de presi n Pa 8 V lvula principal 1 y 2 llama 9 Tuerca de regulaci n del suministro 1...

Page 45: ...paro r pido mayor REGULACI N PRIMERA POSICI N 1a LLAMA Aflojar el tornillo con cabeza cil ndrica sobresaliente 1 Dar al menos una vuelta en el sentido indicado por la flecha con la se al rotaci n en e...

Page 46: ...del local con un m nimo de 0 5 m2 De estas aperturas por lo menos un tercio de la superficie total tiene que colocarse en la parte inferior de una pared externa al nivel del suelo 3 REALIZACI N DE LA...

Page 47: ...47 ESQUEMA DE PRINCIPIO PARA REDUCIR LA PRESI N G L P CON DOS SALTOS PARA QUEMADOR O PARA CALDERA N BT 8721 2 Rev 21 03 90...

Page 48: ...er zur bequemen ffnung des Heizkesselgeh uses eingebaut werden Das Gasventil DUNGS Mod MB umfa t Filter und Gasdruckstabilisator daher braucht an der Gaszuf hrungsleitung nur der Absperrhahn und die v...

Page 49: ...eitung genacht ist es unbedingt notwendig die Gasleitung mit angebrachter Vorsicht und bei offenen T ren und Fenstern zu entl ften Man l se das Verbindungsst ck in der N he des Brenners und ffne etwas...

Page 50: ...er einige Male ein und ausschalten um die korrekte Z ndung zu berpr fen 8 Hinweis Auf einigen Brennermodellen mu der Temperaturw chter f r die zweite Flamme mit zwei Kontak ten im Wechsel ausger stet...

Page 51: ...umbelastung arbeitet kann ein hoher Druck vor der Scheibe notwendig sein Die Einstellvorrichtung ist also so zu verschieben dab man immer einen hohen Druck vor der Scheibe hat Es wird empfohlen die Ei...

Page 52: ...KOPF PRINZIPSCHEMA ZUR EINSTELLUNG DER LUFTKLAPPE VON GASBRENNER Bedienungs und Befestigungknopf des Verbrennungskopfs zur ckschieben um den Luftdurchgang zwischen Schiebe und kopf zu ffnen verschiebe...

Page 53: ...53...

Page 54: ...54...

Page 55: ...55...

Page 56: ...56...

Page 57: ...Drehregler Zufuhr 2 Flamme 11 Schutzdeckel mit Drehknopffunktion der Regulierung der Schnellausl sung am Anfang 12 Gasdruckw chter Maximum nur bei Version B02 und B01 S50 Anmerkung Durch Drehen des Zu...

Page 58: ...rtion zum eingestellten Durchsatz Den Schultzdeckel 11 abschrauben und den unteren Teil als Schl ssel f r den Zapfen ben tzen Drehung im Uhrzeigersinn kleinere schnell ffnende Durchsatzmenge Drehung i...

Page 59: ...Au enwand in gleicher H he des Fu bodens liegen 3 AUSF HRUNGEN DER ANLAGEN F R FL SSIGGAS UM EIN KORREKTES UND SICHERES FUNKTIONIEREN ZU GARANTIEREN Die nat rliche Gasbildung mit Gasflaschen oder Gast...

Page 60: ...60 STROMLAUFSCHALTPLAN ZUR DRUCK VERMINDERUNG DES FLUSSIGGASES IN 2 PHASEN F R BRENNER ODER KESSEL N BT 8721 2D Rev 21 03 90...

Page 61: ...tre en acier avec jointures soud es ou brides PN 40 pression nominale 40 bar Les jointures filet es sont interdites Specifications materiels 1 Vanne de prise du gaz en phase liquide 2 Robinet de distr...

Page 62: ...die Einstellung der Luft f r die zwiete flamme Perno di esclusione accoppiamento motore albero cammes Premendo si ottiene la disinserzione del collegamento motore e albero Exclusion pin coupling motor...

Page 63: ...s an ON OFF contact only you must modify it as per the following diagram modification below by installing an auxiliary relay with a 2 position contact to obtain two stage operation REMARQUE Pour que l...

Page 64: ......

Page 65: ...in esso riportato Technical data in this brochure are given as information only Baltur reserves the right to change specification without notice Ce manuel rev t caract re purement indicatif La maison...

Reviews: