26
GAS FEED SYSTEM AT AVERAGE PRESSURE a few bars
(see BT 8530/1)
When high delivery is required, the Gas Distributing Company requests the installation of a unit comprising a
pressure reducer and a meter, and then connects it to the gas pipe network at average pressure (a few bars).
This unit can be supplied by the Gas Distributing Company or by the user, but should be according to the Gas
Company’s precise instructions. The unit’s pressure reducer should be large enough to supply the maximum gas
delivery required by the burner at the rate of pressure normally estimated for it.
From experience, we would recommend utilising a large-scale reducer in order to attenuate the notable increase
in pressure which occurs when the burner comes to a standstill, with a high delivery. (Regulations require that the
gas valves close in less than one second). As an indication, we would advise using a reducer capable of producing
at delivery (m
3
/h) about double that of the maximum amount estimated for the burner.
If several burners are to be used, each one should have its own pressure reducer; this will enable the gas feed
pressure to the burner to be maintained at a constant level even if only one burner is operating at the time.
Consequently, it is possible to accurately regulate the delivery and therefore the combustion, and thus improve
yield. The dimension of the gas pipeline should be in function with the quantity of gas it has to deliver. We advise
maintaining the load loss at a low level (not more than 10% of the gas pressure value at the burner); it should be
kept in mind that the load loss is added to the pressure existing when the burner stops and therefore a subsequent
start up will occur at a pressure that rises in accordance with an increase in the pipe’s load loss.
Should the gas pressure reach unacceptable values when the burner stops (rapid closure of the gas valves), it is
necessary to install between the reducer and the first valve of the burner an automatic overflow valve and relative
conveying pipe, of suitable section, in the open air. The end of conveying pipe in the open air should terminate in
a suitable place, be protected from rain and have a flame trap. The overflow valve should be regulated in such a
way as to completely unload excessive pressure. Near to the burner should also be fitted a cut-off ball cock, a gas
filter, an anti-vibration joint and a flanged fitting (see BT 8530/1).
DIAGRAM OF CONNECTING MORE THAN ONE BURNER TO THE GAS
PIPE NETWORK AT AVERAGE PRESSURE
1 - Measuring and reducing unit
2 - Interception
3 - Filter
4 - Reducer
5 - Meter
6 - Emergency interception (installed outside)
7 - Ball cock
8 - Filter
9 - Final reducer or stabilizer
10- Anti-vibration joint
11- A couple of flane
D = Distance between pressure stabilizer and valve about 1,5 ÷ 2 m
N° BT 8530/1
REV.: 23/02/2000
Summary of Contents for BGN 40 DSPGN-ME
Page 8: ...8 BGN 40 100 DSPGN ME N 7604 2 Rev 02 02 96 BGN 120 350 DSPGN ME N 7605 5 Rev 17 11 97...
Page 69: ......
Page 70: ......
Page 71: ......