9 / 10
0006160031_201307
ENGLISH
CONVERSION FROM NATURAL GAS TO LPG
To fit the nozzle, proceed as follows:
• close the gas valve and disconnect the flexible joint (a);
• disconnect gas valve (f) from the mixer unit (c) loosening the
four fastening screws (g);
• fit the nozzle for LPG fuel (d) inside the gasket (e).
• assemble the components, making sure to correctly position the
sealing gaskets (e, f);
• switch on the appliance once assembling is complete.
Upon ignition, carry out a leak test of the gas circuit and make sure
that oxygen values (O
2
%) at max. and min. power are within the
tolerances shown in the table below.
ONCE THE CONVERSION HAS BEEN CARRIED OUT,
APPLY THE SUPPLIED ADHESIVE PLATE "LPG" ON THE
BURNER NEAR THE RATING PLATE.
Fuel
O
2
measured with oven at ap-
prox. 100° C at Heating Capacity
min
max
Natural gas
5.0% - 0.3
5.0% - 0.3
L.P.G.
5.5% - 0.3
5.5% - 0.3
O
2
values set for natural gas and LPG operation