GAS TRAIN DESCRIPTION FOR GAS PRESSURE ADJUSTMENT
The burners are combined with monobloc pneumatic proportional
gas valves that allow the quantity of gas supplied and therefore
the power output, to be adjusted.
A pressure signal, detected in the air circuit, is sent to the
pneumatic gas valve, which delivers a quantity of gas proportional
to the airflow processed by the fan.
In order optimise the overall dimensions, the gas train is mounted
directly on the body of the burner.
BPM 90 E
2
5
1
4
A
3
BPM_90_800_013
1
Gas solenoid valve
2
2 Maximum pressure adjustment screw
(counterclockwise to increase, clockwise to decrease)
3
Minimum pressure adjustment screw (counter clockwise
to increase, clockwise to decrease)
CAUTION / WARNINGS
For minimum pressure adjustment, remove cap A
4
Gas inlet
5
Gas inlet pressure port
Minimum output flame
Maximum output flame