ENGLISH
11 / 42
0006160278_201804
GAS TRAIN DESCRIPTION FOR GAS PRESSURE ADJUSTMENT
BPM 140 E
3
A
4
6
5
1
BPM_90_800_01
1
1
Gas solenoid valve
3
Minimum pressure adjustment screw (clockwise to
increase, counter-clockwise to decrease) (A)
Bring the burner at the minimum output and adjust the gas valve
so that the flame appears equally spread on the combustion head,
without any dark spot.
CAUTION / WARNINGS
For minimum pressure adjustment, remove cap A
4
Gas inlet
5
Gas inlet pressure port
6
Max. pressure adjustment (clockwise to increase)
A - MINIMUM OUTPUT FLAME
B - MAXIMUM OUTPUT FLAME