INSTRUCTIONS FOR DETERMINING THE CAUSE LEADING TO IRREGULARITIES IN THE
OPERATION AND THEIR ELIMINATION
Fault
Solution
The burner does not start.
Check the supply voltage.
Check the regulation thermostat (TC)
Check that the connectors are properly inserted.
Check that the network fuse is intact.
Check the gas inlet pressure (2).
Press the reset button.
Check that the gas valve opens. If the valve opens a pressure drop will
occur in point (2).
Check the ignition electrode (see chapter regarding the electrode position)
Check the ionisation current if there is none.
The burner ignites, the ionisation current is present but after the safety
time the burner turns off.
Check that the phase and neutral positions have been respected.