0006081081_200907
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
SUCTION FEED SYSTEM
GRAVITY FEED SYSTEM
Dimension P = 3,5 m. (max.)
H
Total length meters
meters Ø = 16 mm Øi. 18 mm
0,5
21
34
1
18
29
1,5
15
24
2
11,5
19
2,5
8,5
14
3
5,5
9
3,5
-
3,5
H
Total length meters
meters Ø = 16mm Øi. 18 mm
1
30
40
1,5
35
45
2
35
45
2,5
40
50
3
40
50
TABLE OF PIPELINE FOR BT 250 DSG-4T
H - Height difference between minimum fuel tank level and pump axis.
L - Total length of pipeline, including vertical lenght. Subtract 0,25 mt.
for every elbow or gate valve.
N.B. Comply with existing regulations regarding apparatus
required in the pipeline system
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
Pump axis
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
8 Automatic fuel interception device
at burner shut off
9 One-way valve
10 Bottom valve
Pump axis
Pump axis
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
H
Total length meters
meters Ø = 16mm Øi. 18 mm
1
30
40
1,5
35
45
2
35
45
2,5
40
50
3
40
50