REFRACTORY LINING
If a lining is necessary around the combustion head of the burner, it
must comply with the instructions in accordance with the boiler manu-
facturer's instructions.
The refractory lining on the hatch of the combustion chamber protects
the boiler hatch from the high temperatures that develop in the com-
bustion chamber.
It also abbreviates the time necessary to reach the proper temperature,
optimizing combustion.
We recommend using good quality refractory material which can resist
temperatures in excess of 1500°C (42/44% alumina).
Recommendations for correct installation of refractory material:
• Refractory material lining should be applied only to boiler door.
• Application in other parts of the combustion chamber would redu-
ce the thermal exchange with the outside, causing deterioration of
the boiler combustion chamber.
• Application of excess refractory material will also cause a
significant reduction in the volume of the combustion chamber,
preventing optimal combustion due to insufficient volume.
IBR_N_MC_ME_Rivestimento
A
B
C
A
Combustion head
B
Minimum opening 20 mm on diameter
C
Refractory material
FAN ASSEMBLY DIAGRAM
During fan assembly, check that the dimension indicated is respected.
11 / 30
0006081528_201711
ENGLISH
Summary of Contents for btg 15 me
Page 2: ......
Page 28: ...SCHEMI ELETTRICI 26 30 0006081528_201711 ITALIANO...
Page 29: ...27 30 0006081528_201711 ITALIANO...
Page 30: ...28 30 0006081528_201711 ITALIANO...
Page 32: ...30 30 0006081528_201711 ITALIANO...
Page 58: ...WIRING DIAGRAMS 26 30 0006081528_201711 ENGLISH...
Page 59: ...27 30 0006081528_201711 ENGLISH...
Page 60: ...28 30 0006081528_201711 ENGLISH...
Page 62: ...30 30 0006081528_201711 ENGLISH...
Page 63: ......