SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
7
9
8
4
H
P
6
10
3
1
0002900740N2
IMPORTANT
Comply with the regulations in force for any components
missing in the pipelines.
IMPORTANT
Total length of pipeline, including vertical length.
Deduct 0.25 m for each elbow or shutter.
1
Fuel tank.
3
Wire-net filter.
4 Burner.
6
Suction pipe.
7
Burner return pipe.
8
Automatic fuel shut-off device with burner off.
9
Non-return valve.
10 Foot valve.
Height "P" maximum 3.5m
H Difference in level between minimum fuel level in the tank
and pump axis
H
Inner pipe diameter
Ø 14 mm
Total length of each pipe
m
m
1
30
1,5
35
2
35
2,5
40
3
40
INTAKE SUPPLY SYSTEM
3
7
10
4
H
6
1
0002900740N3
IMPORTANT
Comply with the regulations in force for any components
missing in the pipelines.
IMPORTANT
Total length of pipeline, including vertical length.
Deduct 0.25 m for each elbow or shutter.
1
Fuel tank.
3
Wire-net filter.
4 Burner.
6
Suction pipe.
7
Burner return pipe.
10 Foot valve.
H Difference in level between minimum fuel level in the tank
and pump axis
H
Inner pipe diameter
Ø 14 mm
Ø 16 mm
Total length of each pipe
m
m
m
0,5
26
45
1
22
38
1,5
19
31
2
14
25
2,5
11
19
ENGLISH
14 / 30
0006080748_201504
Summary of Contents for BTL 0
Page 2: ......
Page 29: ...SCHEMI ELETTRICI ITALIANO 27 30 0006080748_201504...
Page 30: ...ITALIANO 28 30 0006080748_201504...
Page 32: ...ITALIANO 30 30 0006080748_201504...
Page 59: ...WIRING DIAGRAMS ENGLISH 27 30 0006080748_201504...
Page 60: ...ENGLISH 28 30 0006080748_201504...
Page 62: ...ENGLISH 30 30 0006080748_201504...
Page 63: ......