TROUBLESHOOTING INSTRUCTIONS
ANOMALY
The equipment locks out with the flame
on (red light on). The fault is limited to the
flame control device.
The burner goes into lock-out spraying
liquid fuel but the flame does not ignite
(red light on).The failure is limited to
the ignition device, provided that the
fuel is in good condition (not polluted by
water or other impurities) and sufficiently
atomised.The burner goes into lock-out
spraying liquid fuel but the flame does not
ignite (red light on). Fault in ignition circuit.
The burner goes into lock-out without
spraying fuel.
The burner does not start up.(The
equipment does not perform the start up
program).
POSSIBLE CAUSE
•
Photoresistance severed or fouled with
smoke.
• Boiler fouled.
• Photocell circuit failure.
• Disk or combustion heads dirty.
• Ignition circuit interrupted.
• The ignition transformer cables are
discharging to ground.
• The ignition transformer cables are not
well connected.
• Ignition transformer cut off.
• The electrode faces are not at the right
distance.
• The electrodes discharge to ground
because they are dirty or the insulation
is cracked. Check also under the
fastening terminals of the insulating
elements.
• One phase is missing.
•
Inefficient electric motor.
• Fuel does not reach the pump.
• No fuel in the tank.
• The suction pipe shutter is closed.
• Clogged nozzle.
• Thermostats (boiler or room) or
pressure switches are open.
• Photoresistant-cell in short circuit.
•
Lack of voltage due to the main switch
being off or to the tripping of the meter
safety switch, or voltage failure in the
mains.
•
Thermostat line not wired according to
diagram or open thermostats.
• Equipment internal fault.
REMEDY
• Clean or replace.
• Check all smoke passages.
• Replace the equipment.
• Clean.
• Check the entire circuit.
• Replace them.
•
Connect them in a correct way.
• Replace.
• Return to the correct position.
• Clean or replace.
• Check the supply line.
• Repair or replace.
• Check the suction piping.
• Fill up.
• Open the shutter of the suction pipe.
• Remove and clean thoroughly.
•
Increase the value, or wait until the
thermostats or pressure switches
activate due to the natural temperature
or pressure decrease.
• Replace.
•
Activate switches or wait for power to
return.
• Check the connections and thermostats.
• Replace.
ENGLISH
25 / 30
0006080748_201504
Summary of Contents for BTL 0
Page 2: ......
Page 29: ...SCHEMI ELETTRICI ITALIANO 27 30 0006080748_201504...
Page 30: ...ITALIANO 28 30 0006080748_201504...
Page 32: ...ITALIANO 30 30 0006080748_201504...
Page 59: ...WIRING DIAGRAMS ENGLISH 27 30 0006080748_201504...
Page 60: ...ENGLISH 28 30 0006080748_201504...
Page 62: ...ENGLISH 30 30 0006080748_201504...
Page 63: ......