8 / 16
0006080762_201309
ENGLISH
Funzionamento
EK
7130
z05
/0700
Lockout reset button «EK...» is the key operating element for
resetting the burner control and for activating / deactivating the
diagnostic func-tions.
The multicolor signal lamp (LED) in the lockout reset button is the
key indicating element for both visual diagnostics and interface
diagnostics.
RED
YELLOW
GREEN
MICROCONTROLLER-BASED OIL BURNER CONTROLS LMO ...
Both «EK...» and LED are located under the transparent cover of the lockout reset but-ton.
There are 2 diagnostic choices:
1. Visual diagnostics: Operational status indication or diagnostics of the cause of fault.
2. Interface diagnostics: With the help of the interface adapter OCI400 and PC soft-ware ACS400 or flue gas analyzers of different makes
(refer to Data Sheet N7614).
Visual diagnostics:
In normal operation, the different operating states are indicated in the form of color codes according to the color code table given below.
Interface diagnostics is activated by pressing the lockout reset button for at least 3 seconds (refer to Data Sheet N7614). If, by accident,
interface diagnostics has been activated, in which case the slightly red light of the signal lamp flickers, it can be deactivated by pressing
again the lockout re-set button for at least 3 seconds. The instant of switching over is indicated by a yellow light pulse.
Color code table for multicolor signal lamp (LED)
Status
Color code
Color
Waiting time «tw», other waiting states
....................................
Off
Oil preheater on, waiting time «tw»
...................................
yellow
Ignition phase, ignition controlled
. . .
Flashing yellow
Operation, flame o.k.
green
Operation, flame not o.k.
Flashing green
Undervoltage
Yellow-red
Fault, alarm
Red
Error code output (refer to «Error code ta-ble»)
Flashing red
Extraneous light on burner startup
Green - red
Interface diagnostics
Red flicker light
Legend
OFF RED YELLOW GREEN
Operational status indication
Operating position
Operating position
Interface diagnostics
PC / analyzer
Color code tablei