MODEL
TBG 210 MC
TBG 260 MC
TBG 360 MC
Type-approval PIN
CE-0085BS0067
CE-0085BS0067
CE-0085BS0067
Maximum natural gas heat power
kW
2100
2600
3600
Minimum natural gas heat power
kW
400
450
500
¹) natural gas emissions
mg/kWh
Class 2
Class 2
Class 2
Operation
Two-stage progressive /
modulating
Two-stage progressive /
modulating
Two-stage progressive /
modulating
50 Hz natural gas transformer
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
60 Hz natural gas transformer
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
26 kV 40 mA - 230 V
Maximum natural gas heat rate
Stm³/h
222
261.5
380.9
Minimum natural gas heat rate
Stm³/h
40.3
45.3
52.9
Maximum natural gas pressure
hPa (mbar)
350
360
360
Minimum natural gas pressure
hPa (mbar)
30
40
79
Maximum propane thermal power
kW
2100
2600
3600
Minimum propane thermal power
kW
400
450
500
Maximum propane thermal flow rate
Stm³/h
85.9
106.38
147.2
Minimum propane thermal flow rate
Stm³/h
16.4
18
20.4
Maximum propane pressure
hPa (mbar)
360
360
360
Minimum propane pressure
hPa (mbar)
36.5
80
111
²)propane emissions
mg/kWh
Class 2
Class 2
Class 2
50hz fan motor
kW
3
5.5
7
60hz fan motor
kW
3.5
5.5
9
Absorbed electrical power* 50hz
kW
3.7
6.5
8
Absorbed electrical power* 60hz
kW
4.2
6.5
10.4
50 Hz power supply voltage
3N~ 400V ± 10%
3N~ 400V ± 10%
3N~ 400V ± 10%
60 Hz power supply voltage
3N~ 380V ± 10%
3N~ 380V ± 10%
3N~ 380V ± 10%
Protection rating
IP54
IP54
IP54
Flame detection
IONISATION PROBE
IONISATION PROBE
IONISATION PROBE
Control box
LME 22...
LME 22...
LME 22...
Air flow rate regulation
MECHANICAL CAM
MECHANICAL CAM
MECHANICAL CAM
Operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
85
87.8
87.8
Weight with packaging
kg
92.38
113.13
123.23
Weight without packaging
kg
74
89
96.2
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
* Total absorption at start-up with ignition transformer on.
** The acoustic pressure measured with burner operating at maximum rated thermal output refers to the manufacturer's laboratory environment
conditions and cannot be compared to measurements carried out in different locations.
Propane / natural gas CO emissions ≤ 100 mg/kWh
¹) NATURAL GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh natural gas
1
≤ 170
2
≤ 120
3
≤ 80
²) PROPANE GAS EMISSIONS
Classes defined according to EN 676 standards.
Class
NOx emissions in mg/kWh propane gas
1
≤ 230
2
≤ 180
3
≤ 140
ENGLISH
6 / 34
0006160008_201912
Summary of Contents for CE-0085BS0067
Page 2: ......
Page 35: ...SCHEMI ELETTRICI ITALIANO 33 34 0006160008_201912 ...
Page 69: ...WIRING DIAGRAMS ENGLISH 33 34 0006160008_201912 ...
Page 71: ......