0002910631
17 / 36
0006080095_201207
ENGLISH
own setting. The maximum pressure switch must make use of
the contact which is closed when the switch detects pressure
lower than its own setting. Minimum and maximum gas pressure
switches must be set when the burner is tested.Setting depends
on pressure detected from time to time. The pressure switches
are connected in series, therefore operation (i,e, opening of
the circuit) of the switches does not consent switch-on of the
equipment. Remember that if any of the pressure switches
operates (i.e. the circuit is opened) while burner is operating
(flame lit), the burner stops immediately. When the burner is
tested, correct pressure switch operation must be checked.
By using the adjustment devices, it can be verified whether the
pressure switch that stops the burner actually operates (i.e.
opens the circuit).
• After adjusting, always check the following:
- Burner stop: open air and gas thermostats and pressure
switches.
- locking”: shadow the photocell (UV). To unblock, push the
appropriate button.
SCHEMATIC DIAGRAM OF TWO-STAGE GAS BURNER
1
BALL VALVE
2
VIBRATION DAMPER JOINT
3
GAS FILTER
4
PRESSURE REDUCER OR STABILIZER
5
PAIR OF FLANGES
6
MINIMUM AND MAXIMUM PRESSURE SWITCHES
7
RELIEF VALVE
8
SEAL CONTROL DEVICE AND RELATIVE DW PRESSURE SWITCH
9
TWO STAGE MAIN FLAME VALVE (CLOSED 1
st
STAGE – 2
nd
STAGE)
10 AIR DAMPER CONTROL SERVOMOTOR
11 AIR PRESSURE SWITCH
12 COMBUSTION HEAD
13 AIR REGULATION DAMPER
14 IGNITION FLAME VALVE (PILOT) WITH SUPPLY REGULATOR
Gas train supplied by the manufacturer
The job of the installer
Summary of Contents for COMIST 180
Page 2: ......
Page 36: ...34 36 0006080095_201207 ITALIANO SCHEMA ELETTRICO...
Page 38: ...36 36 0006080095_201207 ITALIANO...
Page 72: ...34 36 0006080095_201207 ENGLISH WIRING DIAGRAM...
Page 74: ...36 36 0006080095_201207 ENGLISH...
Page 108: ...34 36 0006080095_201207 ESPA OL ESQUEMA ELECTRICO...
Page 110: ...36 36 0006080095_201207 ESPA OL...
Page 144: ...34 36 0006080095_201207 FRAN AIS SCH MA LECTRIQUE...
Page 146: ...36 36 0006080095_201207 FRAN AIS...
Page 147: ......