5 / 48
0006080873_00709
H
= Measurement between minimum oil level and pump axis
L
= Max. legth of suction line, including vertical lifts. For each bend of valve deduct 0,25 m.
Ø i
= Internal diameter of pipe
Quote P = 3,5 m (max)
GRAVITY FEED FROM THE BOTTOM OF OIL TANK
1
Oil tank
6
Suction line
2
Feed line
7
Return line
3
Filter
8
Fire valve
4
Burner
9
Non return valve
5
Degasifier
SUCTION FEED
1
Oil tank
6
Suction line
3
Filter
7
Return line
4
Burner
10
Foot valve
GRAVITY FEED OVER THE TOP OF OIL TANK
1
Oil tank
7
Return line
3
Filter
8
Fire valve
4
Burner
9
Non return valve
6
Suction line
10
Foot valve
N.B. For any missing devices in the
pipping, conform to existing regulations.
H
Total
meters
meters
Ø i. 10mm
1
30
35
3
40
4
45
H
Total
meters
meters Øi. 10mm Øi. 12mm
0,5
6
54
1
4
47
1,5
18
38
14
30
,5
10
3
3
6
15
3,5
-
7
H
Total
meters
meters
Ø i. 10mm
1
30
35
3
40
4
45
HYDRAULIC CONNECTIONS
The pipes that connect the tank tothe burner should be in perfect tight condition; we recommend the use of copper
or steel pipes of an adeguate diameter.Fuel gate valves should be fitted at the end of the rigid pipelines.Fit the filter
to the suction pipeline after the gate valve. Connect the flexible fitting to this, which in turn should be connected to
the suction of the burner pump. Connect the flexible fitting to the return pipe after the gate valve, and then connect it
ot the pump return. Filter, flexible pipes and relative connecion nipples are standard burner accessories. The pump
is provided with special connection points for the insertion of control instruments (manometer and vacuumeter).
To ensure reliable and silent operating conditions, the vacuum in suction should not exceed 35 cm Hg equal to
0,46 bar.Maximun suction and return pressure 1,5 bar.
Summary of Contents for COMIST 26SP
Page 29: ...29 48 0006080873_200709 GAS BURNER CONTROLS ...
Page 30: ...30 48 0006080873_200709 GAS BURNER CONTROLS ...
Page 38: ...38 48 0006080873_200709 CAJAS ELECTRÓNICAS DE MANDO Y CONTROL PARA QUEMADORES DE GAS ...
Page 39: ...39 48 0006080873_200709 CAJAS ELECTRÓNICAS DE MANDO Y CONTROL PARA QUEMADORES DE GAS ...
Page 48: ...48 48 0006080873_200709 ...