6 / 18
0006081092_201305
FRANÇAIS
TABLEAU DE RÉGLAGE COURBE ETAMATIC
BRÛLEUR : ………………..
s/n…………………… CHAUDIÈRE : ………………...…..………………………………………................
POINT
VALEUR
CHARGE
ETAMATIC
(digit)
CH 1 INVERSEUR
POINT DE
RÉGLAGE (digit)
CH 3 GAZ
POINT DE
RÉGLAGE
(digit)
CH 4 AIR
POINT DE
RÉGLAGE
(digit)
FRÉQ.
MOTEUR
(Hz)
I
(mA)
(*)
DÉBIT DE
GAZ
(m
3
/h)
PRESS.
AIR
(mbar)
CO (ppm)
O2 %
CO2 % PRESS.
GAZ
TÊTE
(mbar)
ANGLE
PAPILLON
GAZ
SANS
CORRECT.
CO
AVEC
CORRECT.
CO
SANS
CORRECT.
CO
AVEC
CORRECT.
CO
SANS
CORRECT.
CO
AVEC
CORRECT.
CO
P0 (allumage)
ZP (2)
P1 (min)
200
P2
300
P3
400
P4
500
P5
600
P6
700
P7
800
P8
900
P9 (max)
990
UTILISATEUR
……………………...…...……………………………………………………………………………………………………………………………………………..
REMARQUES
…………………………………………………………………………………………………………………………………………………………………………..
........................................................................................................................................................................................................................................
N° PAR
DIGIT
ParamÈtres etamatiC
(*) = Essayer d'obtenir une différence de débit entre un point et l'autre (P9 - P1) :8
Réglage digit potentiomètre
Servomoteur gaz : min…….. ; max :…….
Servomoteur air : min…….. ; max :…….
N° PAR
DIGIT
N° PAR
DIGIT
N° PAR
DIGIT
En cours de fonctionnement au fioul, garder
un excès d’air correct à la cheminée O2 = 5/6 %.
Vérifier les fumées à la puissance minimale et maximale du
brûleur au moyen de la « pompe BACHARACH » afin d'éviter
tout endommagement de la sonde O2.
taBLeaU ParamÈtres PiD
Type de réglage
P=805 P (%)
P=806 I (s)
P=807 D (s)
Très lente
30
400
10
Lente
15
320
40
Normale
7
90
50
Rapide
4
35
17
Très rapide
40
55
15
En cours de fonctionnement au fioul, la sonde CO est
désactivée et le brûleur fonctionnera avec la courbe de O2.