62
ENGLISH
6)
Press F key and the wording Pb will appear. Proceed as per point 1 in order to set table value = 6. Press
&
to confirm this value and the wording t.i will appear.
7)
Proceed as previously described in order to set value t.i = 4 as per table. Press
&
to confirm this value
and move to t.d.
8)
Proceed as previously described in order to set value t.d. = 0.8 as per table. Press
&
to confirm this value
and move to t.c.
9)
Proceed as previously described in order to set value t.c. = 10 as per table. Press
&
to confirm this value
and move to Yh.
10)
Proceed as previously described in order to set value Yh = 100 as per table. Confirm this value by pressing
&
and the display will return to Pb.
11)
Press F key in order to move to Hy2. Proceed as per point 1 and set value Hy2 = 1. Press
&
key to confirm
and remain at Hy2.
12)
Press F key in order to move to SPL 1. Proceed as before and set SPL 1 = 100 °C. Press
&
to confirm and
move to SPL h. Set SPL h = 250 °C in the usual manner. Press
&
to confirm and move to SLOP.
13)
Proceed as before in order to set SLOP = 0 and confirm with
&
key. The controller is now configured and
capable of functioning using set values. Should it be necessary to modify any temperature setting, proceed
as previously described at specific points 4 for SP and 5 for SP2.
NB: The controller is supplied with the instructions given by the manufacturer ASCON that contain the
respective “flow diagram”.
14)
Proceed as follows if wishing to check the default configuration set by us
(1045 or 1046)
:
Press F key repeatedly until the wording ConF appears.
Press
&
key once and the configuration set will appear (
1045 or 1046 - Conf.
). From this position, if
wishing to alter the configuration press
&
once and the wording 9999 - PASS will appear (9 furthest to the
right flashing). It is necessary to enter the PASSword (= 3333) as described at point 1. It is now possible to
change the configuration if desired by following the instructions of point 1.
INSTRUCTIONS FOR ASCON ELECTRONIC TEMPERATURE
CONTROLLER Model MS 30/099 FOR HEAVY OIL IN BURNER
PREHEATER(S)
Summary of Contents for GI 1000 DSPN-D
Page 23: ...23 ITALIANO SCHEMA DI PRINCIPIO REGOLAZIONE ARIA PER MODELLO GI 1000 DSPN D N 0002933410...
Page 24: ...24 ITALIANO SCHEMA DI PRINCIPIO REGOLAZIONE PILOTA GAS PER MODELLO GI 1000 DSPN D N 0002933930...
Page 50: ...50 ENGLISH BURNER GI 1000 DSPN D AIR FEEDING ADJUSTMENT PRINCIPLA DIAGRAM N 0002933410...
Page 51: ...51 ENGLISH N 0002933930 BURNER GI 1000 DSPN D GAS PILOT ADJUSTMENT PRINCIPLE DIAGRAM...
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......