• To check the UV photocell and lock, proceed as follows:
- Start the burner.
- After at least one minute from ignition remove the UV photocell
from its seat and simulate a flame failure by covering it with
a dark cloth. The burner flame must turn off, the equipment
must repeat the ignition phase from the beginning and shut
down as soon as the flame turns on.
- The equipment can only be released manually by pressing
the release button. The burner shutdown efficiency test must
be performed at least twice.
• Check that the boiler thermostats or pressure switches are
operating correctly (they must cause the boiler to shut down
when they intervene).
ENGLISH
Summary of Contents for GI MIST 350 DSPGM
Page 2: ......
Page 40: ...38 44 0006080103_201309 WIRING DIAGRAM ENGLISH...
Page 41: ...39 44 0006080103_201309 ENGLISH...
Page 42: ...40 44 0006080103_201309 ENGLISH...
Page 43: ...41 44 0006080103_201309 ENGLISH...
Page 44: ...42 44 0006080103_201309 RAMPA PRINCIPALE ENGLISH...
Page 46: ...44 44 0006080103_201309 ENGLISH...
Page 84: ...38 44 0006080103_201309 ESPA OL ESQUEMA EL CTRICO...
Page 85: ...39 44 0006080103_201309 ESPA OL...
Page 86: ...40 44 0006080103_201309 ESPA OL...
Page 87: ...41 44 0006080103_201309 ESPA OL...
Page 88: ...42 44 0006080103_201309 ESPA OL RAMPA PRINCIPALE...
Page 90: ...44 44 0006080103_201309 ESPA OL...
Page 128: ...38 44 0006080103_201309 FRAN AIS SCH MA LECTRIQUE...
Page 129: ...39 44 0006080103_201309 FRAN AIS...
Page 130: ...40 44 0006080103_201309 FRAN AIS...
Page 131: ...41 44 0006080103_201309 FRAN AIS...
Page 132: ...42 44 0006080103_201309 FRAN AIS RAMPA PRINCIPALE...
Page 134: ...44 44 0006080103_201309 FRAN AIS...
Page 135: ......