DESCRIPTION OF MODULATING OPERATIONS WITH NATURAL GAS FOR
(see N° 0002910611)
Control box specifi cations
The fi eld of variation in fl ow obtainable is from 1 to 1/3.
The burner is fi tted with an end-of-the-run switch (a micro-switch) which stops the burner starting up
if the fl ow regulator is not in the minimum position.
Before ignition, a pre-ventilation of the combustion chamber occurs (according to Regulations) with air open.
At the end of the ventilation phase, if the air ventilation pressure switch has measured suffi cient pressure, the
ignition transformer will be connected and after the ignition fl ame (pilot) valves and the safety valve will open.
Gas reaches the combustion head, mixes with air supplied by the fan, and is ignited.
Delivery is regulated by the fl ow regulator incorporated in the ignition fl ame (pilot) valve.
The ignition transformer is disconnected after the ignition fl ame and safety valves are inserted.
The burner is now operating with the ignition fl ame (pilot) only.
Flame presence is detected by a relative control device (ionization probe immersed in the fl ame, or UV cell).
The relay programmer passes the “shut down” position and gives voltage to the servomotor which regulates the
delivery (gas/air); the burner is now operating at minimum output.
If the modulation probe allows it (regulated at a temperature or pressure value superior to that existing in the
boiler), the servomotor which regulates the gas/air delivery starts turning and determines a gradual increase
in the gas delivery and in the relative combustion air until it reaches the maximum delivery value at which the
burner has been regulated.
N.B.
The “V” cam of the servomotor regulating gas/air delivery (see BT 8562/1)
inserts almost immediately the principle gas valve, which in turn opens completely. Gas delivery is not de-
termined by the principle valve but by the position of the gas delivery regulation valve (see BT 8814).
The burner remains in the maximum delivery position until the temperature or pressure reaches the limit set
for the intervention of the modulation probe and makes the servomotor regulating gas/air delivery rotate in the
opposite sense of direction.
Thus gas delivery and the relative combustion air are gradually reduced until they reach minimum level.
Even with delivery at a minimum, if the limit (temperature or pressure) at which the shut down device (thermostat
or pressure switch) has been regulated is reached, the burner will be brought to a standstill.
When the temperature or pressure drops below the intervention limit set on the shut down device, the burner will
start up again, according to the programme previously described.
During normal operations, the boiler modulation probe fi tted to the boiler detects the variations requested and
automatically proceeds with adapting the fuel and combustion air delivery by inserting the servomotor which
regulates delivery (gas/air).
This will rotate in such a way as to obtain an increase or a decrease.
With this manoeuvre, the gas/air delivery regulating system tries to equilibrate the quantity of heat supplied to
the boiler with that which the boiler gives to be utilized.
If the fl ame does not appear the control box goes to “shut down” (the burner stops completely and the relative
indicator light is turned on.
To unblock the control box, press the appropriate push button.
Control box &
relative
Programmer
LFL 1.333
Cyclic relay
Safety Time
in seconds
3
Pre-Ventilation
Time with shut-
ter open
in seconds
31,5
Pre-ignition
Time
in seconds
6
Post-ignition
Time
in seconds
3
Time between
1st fl ame & Start of
Modulation
in seconds
12
Summary of Contents for GI MIST 350 DSPGM
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......