INSTRUCTIONS FOR SETTING DUNGS GAS VALVES
mod. MVD ... and MVDLE ...
The MVD gas valves open and close rapidly.
To regulate the gas fl ow, unscrew and remove cap “A”
and loosen nut “B”.
Then, using a screwdriver turn screw “C”. Unscrewing
it increases the gas fl ow, tightening it decreases the
fl ow.
After regulating, lock nut “B” in place and reposition
cap “A”.
HOW THE VALVE FUNCTIONS mod. MVDLE
The gas valve has a rapid initial trip (opening can be
adjusted from 0 to 40% using pin “G”). Full opening
from that point on takes place slowly over approxima-
tely 10 seconds.
N.B.
There will not be suffi cient supply for ignition if
the fl ow feed device “E” is set at its minimum
position. Therefore, it is essential to open the
maximum fl ow rate control device “E” suffi cien-
tly to ensure ignition.
Setting the initial rapid release trip
To set the initial rapid release, unscrew the protection
cap “F” and use the back of this cap as a tool to turn
pin “G”.
Turning clockwise decreases the gas fl ow, turning
counter-clockwise increases it.
This done, return cap “F” to its original position.
Setting maximum gas fl ow
To adjust the gas fl ow rate, loosen screw “D” and turn
knob “E”. Turning clockwise decreases the gas fl ow,
turning counter-clockwise increases it.
This done, tighten screw “D”.
Mod. MVDLE....
Mod. MVD....
8875.tif
H
= Identifi cation plate
I
= Flow direction indicator
D
= Identifi cation plate
E
= Flow direction indicator
N° 8875
Rev. 06/11/90
Summary of Contents for GI MIST 350 DSPGM
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......