INSTRUCTIONS FOR SETTING LANDIS & GYR mod. SKP 10.110 B27
- SKP 10.111B27 SINGLE STAGE GAS VALVES
DESCRIPTION OF HOW THE VALVE OPERATES
Single-stage valves
When the valve receives the signal to open, the pump cuts in and the magnetic valve closes. The pump tran-
sfers the oil from under the piston to above it, forcing the piston downward, which compresses the closure return
spring with the rod and plate. The valve remains in the open position while the pump and magnetic valve remain
powered.
When the unit receives the signal to close (or if power supply is cut off) the pump shuts down, the magnetic
valve opens decompressing the chamber above the piston. The plate is closed both by the return spring and
by gas pressure.
The fl ow rate for this valve is calculated to ensure full closure in less than one second.
This type of valve cannot regulate the gas fl ow
rate (closure/opening).
Screw “D” on terminal “IV” sets the “clean con-
tact” position which can be used for an outside
signal.
A = Driver identifi cation plate
B = Flow direction indicator
C = Valve body identifi cation plate
N° 8880
Rev. 06/11/90